Horizontal Termination - Empire Comfort Systems MILLIVOLT DVCD FP3-4 Series Installation Instructions Manual

Direct-vent zero clearance gas fireplace heater
Table of Contents

Advertisement

NOTICE: The termination cap must pass through the wall
firestop from the exterior of the building. Adjust the termination
cap to its final exterior position on the building.
The termination cap must be positioned so that the arrow is
pointing up. Failure to properly position the parts may result
in a hazardous situation.
Attach the termination cap with the four wood screws provided.
Before attachment of the termination, run a bead of silicone
sealant rated above 250°F on its outside edge to make a seal to
the exterior wall.
Replace the wood screws with the appropriate fasteners for
use on stucco, brick, concrete or other types of siding. Failure
to use the proper fasteners may result in a hazardous situation.
Install a vinyl siding standoff if the exterior walls are finished
with vinyl siding or materials that could become discolored
or warp.
Install the vinyl siding standoff between the vent termination
and the exterior wall. See Figure 52. This horizontal vent
termination bolts onto the flat portion of the vinyl siding
standoff, so an air space will exist between the wall and the
termination cap.
ATTENTION
VINYL SOFFIT, VINYL CEILING, VINYL OVERHANG DISCLAIMER
Clearances are to heat resistant material (i.e. wood, metal).
This does not include vinyl. Empire Comfort Systems will not
be held responsible for heat damage caused from terminating
under vinyl overhangs, vinyl ceilings or vinyl ventilated/
unventilated soffits.
38712-4-0920

HORIZONTAL TERMINATION

CAUTION
CAUTION
CAUTION
Figure 52
Snorkel terminations are available for installations requiring
a vertical rise of the building. See Figure 53. Provide proper
drainage to prevent water from entering the snorkel termination
if it will be installed below grade (i.e. in a basement). Refer to
(Figure 54). Do not attempt to enclose the Snorkel within the wall
or any other type of enclosure.
(Snorkel or Snowlevel Clearance Required)
(Snorkel or Snowlevel Clearance Required)
SNORKEL
12" MINIMUM
OR EXPECTED
SNOW LEVEL
ADEQUATE
DRAINAGE
Figure 53
SNORKEL
12" MINIMUM
OR EXPECTED
SNOW LEVEL
Figure 54
Page 31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Intermittent pilot dvcd fp7-4 series

Table of Contents