Performance Specifications - Mitsubishi AJ65SBT2B-64RD3 User Manual

Rtd input module
Table of Contents

Advertisement

2.2 Performance Specifications

The performance specifications for the AJ65SBT2B-64RD3 are shown
in the following table.
Item
Measurement method
Measured temperature
value
Usable RTD
Detecting current
Detecting range, degree
of conversion accuracy,
resolution
Conversion speed
Temperature input point
Maximum number of
writes for Flash memory
CC-Link station type
No. of occupied stations
Connection cable
Withstand voltage
Isolation system
Noise immunity
Wire break detection
Table 2.2 Performance specifications
16-bit signed binary (-2000 to 8500)
Pt100 (JIS C 1604-1997), JPt100 (JIS C 1604-1981), Ni100 (DIN
Detecting range
-200 to 850
Pt100
-20 to 120
0 to 200
-180 to 600
JPt100
-20 to 120
0 to 200
Ni100
-60 to 180
1 station (RX/RY: 32 points each, RWr/RWw: 4 points each)
500 V AC for 1 minute across all power supply and communication
system terminals and all RTD input terminals
Between communication system and all RTD inputs: Photocoupler
isolation
Between power supply system and all RTD inputs: Trans isolation
Between channels: No isolation
Noise voltage : 500Vp-p, tested by noise simulator of noise width of
1 s and noise frequency of 25 to 60Hz
Capable (channels respectively)
3
AJ65SBT2B-64RD3
3-wire
43760 1987)
1mA
Degree of conversion
accuracy
Ambient
temperature
0 to 55
1.4
0.6
0.6
1.0
0.6
0.6
0.5
40ms/1channel
4 channels/1 module
MAX. 10,000 times
Remote device station
CC-Link dedicated cable
*1*2
Resolution
Ambient
temperature
25 5
0.5
0.2
0.2
0.4
0.1
0.2
0.2
0.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aj65s-64rd3-u-hw13jy77