No.
Name
PW LED
RUN
LED
Operation
status
1
display LED
L RUN
LED
L ERR.
LED
V
Offset/gain
I
adjusting
CH
2
LEDs
OFFSET
GAIN
SELECT/
Used to make offset/gain setting in the test mode.
3
SET switch
UP/DOWN
Used to adjust the offset value and gain value of the channel specified by
4
switch
the SELECT/SET switch.
Table 3.1 Part names
On: Power supply on
Off: Power supply off
On:
Normal operation
Flashing:
0.1-second interval: CH
range error occurs.
Normal
0.5-second interval: Out of average
mode
processing setting range error occurs.
Off:
Indicates that 24VDC power supply
interrupted, watchdog timer error occurred,
write error for flash memory occurred.
On:
Indicate that the SELECT/SET switch is in
the SET position.
Flashing:
The offset value is during correction, or the
gain value is out of the setting range. (The
Test
gain value is out of range of the
mode
measurement temperature or less than 10
when the offset value is subtracted from the
gain value.)
Off:
Indicates that the SELECT/SET switch is in
the SELECT or center position.
On: Normal communication
Off: Communication cutoff (time expiration error)
On:
Flicker at fixed intervals:
Flicker at unfixed intervals:
Off:
Normal
Normally OFF.
mode
Test
The LEDs lit change every time the SELECT/SET
mode
switch is moved to SELECT.
7
Description
Indicates that station number setting
is outside the range.
Indicates that station number setting
was changed from that at power-on.
Indicates that you forgot fitting the
terminating resistor or the module or
CC-Link dedicated cable is affected
by noise.
Indicates normal communications.