Required Reprogramming Of Tracer Adaptiview Controls; Reprogramming Retrofit Tracer Adaptiview Controls (Cvr Firmware) - Trane CVHE Installation Instructions Manual

E-frame retrofit adaptive frequency drive
Table of Contents

Advertisement

Table 23. CT meter scales for TechView or Tracer TU
Actual Motor
RLA Amps (A)
100–133
134–184
185–267
268–334
335–467
468–667
668–1000
Required Reprogramming of
Tracer AdaptiView Controls
Reprogramming Retrofit Tracer
AdaptiView Controls (CVR Firmware)
Important:
For a chiller retrofitted with an AFDH drive to operate
correctly and efficiently, it is critical that the actual
specific nameplate data values for the chiller be
entered in the UC800 menu parameters listed in the
table below (i.e. motor data and compressor impeller
data). If the unit nameplate is missing, unreadable, or
of a vintage that did not include all of the required data
categories, contact Trane Global Parts Technical
Services. To contact them, send a message to
ATechnicalService@trane.com. Provide the chiller
serial number and request a copy of the shipped-with
bill of materials for this unit.
Make sure your laptop is loaded with the most current
version of Tracer TU tool software so that you have the
most up-to-date version of CVR MP firmware available
to install into the UC800.
Note: CVR MP firmware is always used in the UC800 on
Tracer AdaptiView control systems or display
upgrades that were retrofitted in place of all earlier
versions of chiller controllers with only one specific
exception: factory installed CH530 controls.
Factory installed CH530 control systems used CTV
MP firmware so the new Tracer AdaptiView
controls will also use CTV MP firmware.
AFDH-SVN02D-EN
X13580269
CT Extension
02
03
04
05
06
07
08
CT Ratio
CT Rating
(A:A)
150:0.1
200:0.1
275:0.1
400:0.1
500:0.1
700:0.1
1000:0.1
Installation
(A)
CT Meter Scale
150
150
200
200
275
275
400
400
500
500
700
700
1000
1000
41