a. Install the appropriate conduit hubs before
reinstalling the access door pieces on top of the
cabinet.
2. Route the input wire leads into the cabinet and connect
them to circuit breaker terminals L1, L2, and L3.
a. The torque specification for these terminal
connections is 23 foot-pounds.
Figure 19. Two-piece incoming wire access cover
Note: The complete cabinet top is removable. This may
help with the installation of the input power leads.
AFDH-SVN02D-EN
Figure 20. Factory installed input disconnect circuit
breaker
1.
Input disconnect circuit breaker
2.
Nameplate
3.
Input power terminals. Terminal connections should be torqued
to 23 foot·pounds

Grounding AFDH Cabinet

WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
to accept other types of conductors.
1. Run a suitable, unbroken, grounding conductor from
the drive cabinet's ground connection terminal to the
motor's ground terminal, and then on to earth ground.