- The compressor will start automatically if it has stopped for 30
minutes even if the room temperature is below the compressor
OFF temperature.
- If the temperature of the Outdoor Heat Exchanger less than -3°C,
Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor Heat
Exchanger temperature is T
Temperature region as table below:
During starting of Heating mode and after deice, Outdoor Fan ON
for 90 sec. (Hi).
- If the Indoor heat exchanger becomes 68°C or more, the
compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting)
- 4-way valve ON during Heating operation, except deicing operation.
- When the unit is switched to "OFF" during Heating operation, 4-
way valve stay at Heating position for 5 minutes.
When Heating operation starts, Indoor Fan will not start until the
indoor heat exchanger reaches 30°C as diagram shown.
PDF created with pdfFactory Pro trial version
Overload Protection Control
4-way Valve Control
Hot Start Control
or more according to Outdoor Air