Zone Response Type Definitions - ADEMCO Vista-2000 Programming Manual

Hide thumbs Also See for Vista-2000:
Table of Contents

Advertisement

Type 00
Zone Not Used
Type 01
Entry/Exit Burglary
Type 02
Type 03
Perimeter Burglary
Type 04
Interior, Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
Auxiliary Alarm
Type 09
Supervised Fire
Type 10
Interior w/Delay
www.PDF-Zoo.com

ZONE RESPONSE TYPE DEFINITIONS

Program a zone with this zone type if the zone is not used.
This zone type provides entry delay whenever the zone is faulted if the control
is armed in the AWAY or STAY modes. When the panel is armed in the
Instant or Maximum modes, no entry delay is provided. Exit delay begins
whenever the control is armed, regardless of the arming mode selected. These
delays are programmable. This zone type is usually assigned to sensors or
contacts on doors through which primary entry and exit will take place.
Not used in this system
This zone type gives an instant alarm if the zone is faulted when the panel is
armed in the AWAY, STAY, INSTANT or MAXIMUM modes. This zone type
is usually assigned to all sensors or contacts on exterior doors and windows.
This zone type is active when the panel is armed in the AWAY or MAXIMUM
modes. Entry delay (using the programmed entry time) results if the panel is
armed in the AWAY mode and the entry/exit zone is faulted first. Otherwise
this zone type gives an instant alarm. Exit delay is present for any arming
mode. This zone type is usually assigned to a zone covering an area such as a
foyer, lobby, or hallway through which one must pass (upon entry, after
faulting the entry/exit zone) to reach the keypad to disarm the system. Since
this zone type is designed to provide an instant alarm if the entry/exit zone is
not violated first, it will protect an area in the event an intruder hides on the
premises prior to the system being armed, or gains access to the premises
through an unprotected area. This zone type is bypassed automatically
when the panel is armed STAY or INSTANT.
This zone type will give an instant alarm if faulted when armed in the AWAY,
STAY, INSTANT or MAXIMUM (night) modes. During the disarmed state
(day), the system will provide a latched trouble sounding from the keypad
(and a central station report, if desired). This zone type is usually assigned to
a zone which contains a foil-protected door or window (such as in a store), or
to a zone covering a "sensitive" area such as a stock room, drug supply room,
etc. This zone type can also be used on a sensor or contact in an area where
immediate notification of an entry is desired.
This zone type sends a report to the Central Station but provides no keypad
display or sounding. This zone type is usually assigned to a zone containing
an Emergency button.
This zone type sends a report to the Central Station, and provides a rapid
beeping sound at the keypad, and an audible external alarm. This zone type
is usually assigned to a zone that has an Emergency button.
This zone type sends a report to the Central Station and provides a rapid
24-hour
beeping sound at the keypad. (No bell output is provided). This zone type
is usually assigned to a zone containing a button for use in personal
emergencies, or to a zone containing monitoring devices such as water or
temperature sensors, etc.
This zone type provides a fire alarm on short circuit and a trouble condition
on open circuit. The bell output will pulse when this zone type is faulted. This
zone type is always active and cannot be bypassed. This zone type can be
assigned to control panel wired zone 5 and to certain wireless zones.
This zone type gives entry delay (using the programmed entry time), if tripped
when the panel is armed in the Away mode, regardless of whether or not an
entry/exit delay zone was tripped first. This zone type is also active during
MAXIMUM mode, but n o entry delay is provided (an alarm occurs
immediately if the zone is tripped). Exit delay is present for any arming
mode. This zone type is bypassed automatically when the panel is
armed Stay or Instant .
firealarmresources.com
– 11 –