Samsung AM080FX A Series Service Manual page 41

System air conditioner outdoor unit
Table of Contents

Advertisement

Product Specifications
2-5 Product Specification (cont.)
2-5-1 Outdoor Unit (cont.)
Image
Model Name
Power Supply
Φ, V, Hz
Mode
HP
Cooling
Performance
Capacity
Btu/h
(Nominal)
Heating
Btu/h
Power Input
Cooling 1)
(Nominal)
Heating 2)
Current Input
Cooling 1)
(Nominal)
Heating 2)
Cooling
Power
Running Current
Heating
Max
Cooling 1)
Power Consumption
Heating 2)
MCA(Minimum Circuit Amps)
MFA/MOP(Maximum Fuse Amps)
Nominal Cooling 1)
COP
Nominal Heating 2)
W/W
ESEER
Type
Output
Compressor
Model Name
Type
Oil
Initial Charge
Type
Output x n
m³/min
Fan
Air Flow Rate
External Static
mmAq
Max.
Pressure
Liquid Pipe
Φ, mm
Φ, inch
Gas Pipe
Φ, mm
Φ, inch
Φ, mm
Discharge Gas Pipe
Piping
Φ, inch
Connection
ODU-IDU
Max.
Piping length
After branch
Max.
Total piping length
System
Actual
Outdoor unit in high-
est position
ODU-IDU
Level difference
Indoor unit in high-
est position
IDU-IDU
Max.
Type
Refrigerant
Factory Charging
Cooling
Sound Pressure
Sound
Heating
dB(A)
Sound Power
DVMS HP
Net Weight
DVMS HR
External
DVMS HP
Shipping Weight
DVMS HR
Dimension
Net Dimension (WxHxD)
Shipping Dimension (WxHxD)
DVMS HP
Operating
Cooling
DVMS HR
Temp. Range
Heating
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
Samsung Electronics
AM140FXVAGH
3/AC380~415/50
-
HEAT PUMP
HP
14
kW
40.0
136,000
kW
45.00
153,000
8.90
kW
9.50
14.30
A
15.20
14.30
A
15.20
25.00
8.90
kW
9.50
31.30
A
40.00
4.49
4.74
7.02
-
INV x 1
kW
5.8
-
DS-GB066FA****
-
FVC68D
cc
3900
-
Propeller + BLDC
W
630 x 2
226
l/s
3,767
-
Pa
-
Type
Braze connection
12.7
1/2"
Type
Braze connection
28.58
1+1/8"
19.05
3/4"
m
200(220)
m
90
m
1000
m
110
m
110
m
50
-
R410A
kg
7.7
-
-
-
235
kg
214
254
kg
260
mm
1295x1695x765
mm
1363x1857x832
-5.0 ~ 48.0
-15.0 ~ 48.0
-25.0 ~ 24.0
Product Specifications
AM160FXVAGH
AM180FXVAGH
3/AC380~415/50
3/AC380~415/50
HEAT PUMP
HEAT PUMP
16
18
45.0
50.4
153,000
171,900
50.00
56.70
170,000
193,500
11.00
12.80
11.50
11.90
17.60
20.70
18.40
19.10
17.60
20.70
18.40
19.10
32.00
39.10
11.00
12.80
11.50
11.90
40.00
48.90
40.00
50.00
4.09
3.91
4.35
4.76
6.78
6.59
INV x 2
INV x 2
4.7 x 2
5.8 x 2
DS-GB052FA****
DS-GB066FA****
FVC68D
FVC68D
6200
6200
Propeller + BLDC
Propeller + BLDC
630 x 2
630 x 2
250
270
4,167
4,500
-
-
-
-
Braze connection
Braze connection
12.7
15.88
1/2"
5/8"
Braze connection
Braze connection
28.58
28.58
1+1/8"
1+1/8"
22.22
22.22
7/8"
7/8"
200(220)
200(220)
90
90
1000
1000
110
110
110
110
50
50
R410A
R410A
7.4
8.7
-
-
-
-
-
-
278
300
184
306
297
319
303
325
1295x1695x765
1295x1695x765
1363x1857x832
1363x1857x832
-5.0 ~ 48.0
-5.0 ~ 48.0
-15.0 ~ 48.0
-15.0 ~ 48.0
-25.0 ~ 24.0
-25.0 ~ 24.0
38
Samsung Electronics
AM200FXVAGH
AM220FXVAGH
3/AC380~415/50
3/AC380~415/50
HEAT PUMP
HEAT PUMP
20
22
56.0
61.6
191,000
210,000
63.00
69.30
215,000
236,000
15.19
17.35
13.90
16.70
24.40
27.80
22.30
26.80
24.40
27.80
22.30
26.80
42.50
44.50
15.19
17.35
13.90
16.70
52.50
52.50
75.00
75.00
3.69
3.55
4.53
4.15
6.56
6.25
INV x 2
INV x 2
5.8 x 2
5.8 x 2
DS-GB066FA****
DS-GB066FA****
FVC68D
FVC68D
6200
6200
Propeller + BLDC
Propeller + BLDC
630 x 2
630 x 2
275
280
4,583
4,667
-
-
-
-
Braze connection
Braze connection
15.88
15.88
5/8"
5/8"
Braze connection
Braze connection
28.58
28.58
1+1/8"
1+1/8"
28.58
28.58
1+1/8"
1+1/8"
200(220)
200(220)
90
90
1000
1000
110
110
110
110
50
50
R410A
R410A
8.4
8.4
-
-
-
-
-
-
300
300
306
306
319
319
325
325
1295x1695x765
1295x1695x765
1363x1857x832
1363x1857x832
-5.0 ~ 48.0
-5.0 ~ 48.0
-15.0 ~ 48.0
-15.0 ~ 48.0
-25.0 ~ 24.0
-25.0 ~ 24.0
39