Samsung AM080FX A Series Service Manual page 377

System air conditioner outdoor unit
Table of Contents

Advertisement

Key Options
8-4 How to check the view mode using a tact switch (cont.)
AM080/100/120/200FXWASS
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Setting longpiping
condition
(Setting is unnecessary
Main
if high-head condition
is set.)
Energy saving
Main
setting
Disable
Main
Expand operational
temperature range for
Main
cooling operation
Channel address
Main
Disable
Main
Circulation water
Individual
flow control
Samsung Electronics
0
0
0
1
0
9
0
2
0
0
1
0
0
1
0
0
1
1
0
1
0
0
1
2
0
1
A
U
1
3
0 ~ 15
Manual setting for channel 0~15
0
0
1
4
0
1
0
0
0
1
1
5
0
2
0
3
Function of the option
Disable (Factory default)
Long piping level 1
Long piping level 2
Disable (Factory default)
Enable
Disable
Disable
Disable
Enable
Automatic setting (Factory
default)
Disable
Disable
Disable (Factory default)
7-10 V
5-10 V
3-10 V
Remarks
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170 m
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170 m
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in heating
mode.
This function is not applicable for
this model
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc)
This function is not applicable for
this model
When variable flow control valve
is applied
396