Preparation For Installation And Wiring; Ambient Conditions; Minimum Mounting Clearances - Delta Electronics VFD-M Series User Manual

High performance / low-noise micro-type ac motor drives
Table of Contents

Advertisement

1.2 Preparation for Installation and Wiring

1.2.1 Ambient Conditions

Install the AC motor drive in an environment with the following conditions:
Operation
Storage
Transportation
Pollution
Degree

1.2.2 Minimum Mounting Clearances

Revision May 2008, ME14, SW V3.04
Air Temperature:
Relative Humidity:
Atmosphere
pressure:
Installation Site
Altitude:
Vibration:
Temperature:
Relative Humidity:
Atmosphere
pressure:
Vibration:
2: good for a factory type environment.
150mm
150mm
-10 ~ +50°C (14 ~ 122°F) for UL & cUL
-10 ~ +40°C (14 ~ 104°F) for 5.5kw models and above
<90%, no condensation allowed
86 ~ 106 kPa
<1000m
2
<20Hz: 9.80 m/s
(1G) max
2
20 ~ 50Hz: 5.88 m/s
-20°C ~ +60°C (-4°F ~ 140°F)
<90%, no condensation allowed
86 ~ 106 kPa
2
<20Hz: 9.80 m/s
(1G) max
2
20 ~ 50Hz: 5.88 m/s
Air Flow
Chapter 1 Introduction|
(0.6G) max
(0.6G) max
1-5