Acceleration S-Curve
Settings 00 to 07
This parameter is used whenever the motor load needs to be accelerated or decelerated
smoothly. The desired accel/decel effect is selectable from 0 to 7, in which the larger the
number, the greater the effect achieved. If the default value of Pr.111 Deceleration S Curve is
unchanged ("0"), then Pr.14 sets both acceleration and deceleration S-Curves. If Pr.111 is set
to any value other than "0", then Pr.14 will set the acceleration S-Curve and Pr.111 will set the
deceleration S-Curve.
Pr.15
Jog Accel / Decel Time
Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec
This parameter sets the acceleration or deceleration time for Jog operation.
Pr.16
Jog Frequency
Settings 0.00 to 400.0 Hz
Revision May 2008, ME14, SW V3.04
Actual Acceleration/Deceleration Time=
Acceleration/Deceleration Time x(Master Freq.-Min.Output Freq.)
Time
Pr.11
or
Pr. 13
Deceleration Time
Freq.
Acceleration/Deceleration characteristics
(1), (2) Disabling S curve
(3), (4) Enabling S curve
Chapter 4 Parameters|
Max. Output Freq.
Factory Setting: 00
Unit: 0.1 or 0.01 sec
Factory Setting: 1.0 sec
Unit: 0.1 Hz
Factory Setting: 6.00 Hz
4-25