Delta Electronics VFD-M Series User Manual page 44

High performance / low-noise micro-type ac motor drives
Table of Contents

Advertisement

Parameter
Explanation
Pr.78
PLC Operation Mode
PLC FWD/REV
Pr.79
Motion
Identity Code of the
Pr.80
AC Motor Drive
Time Duration of 1st
Pr.81
Step Speed
Time Duration of 2nd
Pr.82
Step Speed
Time Duration of 3rd
Pr.83
Step Speed
Time Duration of 4th
Pr.84
Step Speed
Time Duration of 5th
Pr.85
Step Speed
Time Duration of 6th
Pr.86
Step Speed
Time Duration of 7th
Pr.87
Step Speed
Communication
Pr.88
Address
Pr.89
Transmission Speed
Transmission Fault
Pr.90
Treatment
Pr.91
Time Out Detection
Communication
Pr.92
Protocol
Revision May 2008, ME14, SW V3.04
Settings
00: Disable PLC operation
01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by step
04: Continuously execute one program cycle
step by step
00 to 127
Read only
00 to 9999 sec
00 to 9999 sec
00 to 9999 sec
00 to 9999 sec
00 to 9999 sec
00 to 9999 sec
00 to 9999 sec
01 to 254
00: 4800 bps
01: 9600 bps
02: 19200 bps
03: 38400 bps
00: Warn and Continue Operating
01: Warn and RAMP to Stop
02: Warn and COAST to Stop
03: Keep Operation without Warning
0.0: Disable
0.1 to 120.0 sec
00: MODBUS ASCII mode, <7,N,2>
01: MODBUS ASCII mode, <7,E,1>
02: MODBUS ASCII mode, <7,O,1>
03: MODBUS RTU mode, <8,N,2>
04: MODBUS RTU mode, <8,E,1>
05: MODBUS RTU mode, <8,O,1>
Chapter 4 Parameters|
Factory
Setting
00
00
##
00
00
00
00
00
00
00
01
01
03
0.0
00
Customer
4-9