Chapter 4 Parameters|
Parameter
Explanation
Accel 1 to Accel 2
Pr.93
Frequency Transition
Decel 1 to Decel 2
Pr.94
Frequency Transition
Pr.95
Auto Energy Saving
Counter Countdown
Pr.96
Complete
Preset counter
Pr.97
countdown
Total Time Count from
Pr.98
Power On (Days)
Total Time Count from
Pr.99
Power On (Minutes)
Pr.100
Software Version
Auto Adjustable
Pr.101
Accel/Decel
Auto Voltage
Pr.102
Regulation (AVR)
Auto tune Motor
Pr.103
Parameters
Pr.104
R1 value
Pr.105
Control Mode
Pr.106
Rated Slip
Pr.107
Vector Voltage Filter
Vector Slip
Pr.108
Compensation Filter
Selection for Zero
Pr.109
Speed Control
4-10
Settings
0.01 to 400.0
0.00: Disable
0.01 to 400.0
0.00: Disable
00: Disable auto energy saving
01: Enable auto energy saving
00 to 9999
00 to 9999
00 to 65535 days
00 to 1440 minutes
00: Linear Accel/Decel
01: Auto Accel, Linear Decel
02: Linear Accel, Auto Decel
03: Auto Accel/Decel
04: Linear Accel/Decel Stall Prevention
during Deceleration
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled when stops
03: AVR function disabled when decel
00: Disable
01: Auto tune for R1
02: Auto tune for R1 + No Load testing
00 to 65535 mΩ
00: V/F Control
01: Sensor-less Control
0.00 to 10.00 Hz
5 to 9999 (per 2ms)
25 to 9999 (per 2ms)
00: No output
01: Control by DC voltage
Factory
Setting
0.00
0.00
00
00
00
Read
Only
Read
Only
##
00
00
00
00
00
3.00
10
50
00
Revision May 2008, ME14, SW V3.04