Installation Instructions, Volume 2
fire change of state.
3. Outputs programmed for Fire Trouble may not be programmed to activate on Fire Alarm, Supervisory,
or non-fire change of state.
4. Outputs programmed to activate on non-Fire change of state events may not be programmed to activate
on Fire Alarm, Supervisory or Fire Trouble events.
Note: Relay Events activated on a Trouble or Trouble Restore may only activate outputs programmed as
Supplemental. These outputs will be activated on the Trouble and the output will remain on until a GEMC-
FK1 Fire keypad is unlocked and the Function Menu option "Reset Supplemental Output" is selected.

BURGLARY OUTPUTS

Burglary outputs require either a GEMC-BM or GEMC-BM/PS (Burg Module with separate battery charger circuit,
battery monitor circuit and one separate 12V 4AH, 7AH or 8AH battery).
The GEMC-BM Burglary Module (or GEMC-BM/PS) Burglary Module has 4 programmable outputs:
• One bell output, supervised for open
• Two unsupervised active low outputs, PGM1 and PGM2
• One unsupervised 12V or one unsupervised Form C relay output, selectable for 12V nominal or dry contacts
GEMC-BSLC Burg SLC Module Outputs
Based on the available current the GEMC-BSLC provides, up to 44 GEMC-BSLC-RLY modules may be used
with any one GEMC-BSLC. If these 44, up to 40 (GEMC-BSLC-RLY) may have their integral relay supervised; all
are supervised for connection to the SLC loop
Only the first 40 external outputs (the first 5 output groups) can have supervised outputs (for relay contact failure)
that also display as outputs with descriptions on the GEMC-FK1 keypad. Supervised Burglary outputs require
that they be configured as external relay 1-40, therefore the first 40 outputs should be carefully evaluated before
they are used. Note: Burg outputs cannot be disabled from the keypad.
The GEMC-OUT8 is wired to the Burg 4-wire bus, and is supervised for connection to this bus (an open or short
on the 4-wire bus that prevents the operation of the GEMC-OUT8 will generate a trouble). The GEMC-OUT8 also
provides 8 independent programmable active low unsupervised external outputs for controlling bells, door latches,
lights, strobes and other similar devices. The panel controls the activation of each external output. To use the
outputs as Burg outputs, the module must be wired and programmed to the Burg 4-wire bus (see WI1707 for
more information).
The GEMC-RM3008 is wired to the Burg 4-wire bus, and is supervised for connection to this bus (an open or
short on the 4-wire bus that prevents the operation of the GEMC-RM3008 will generate a trouble). The GEMC-
RM3008 also provides one group of eight unsupervised Form C dry relay contact outputs.
There is one Burglary SLC output device, the GEMC-BSLC-RLY. The GEMC-BSLC-RLY provides a single unsu-
pervised relay output that requires a listed power supply, properly installed, to power the output, or the use of the
Burg Module AUX PWR.
The device monitors the relay to confirm that contact was activated, and will generate a trouble if it is mapped to
one of the first 40 relays. This should not be confused with output supervision for an open or a short on the cir-
cuit.
The SLC devices may be configured (programmed and wired) as either Class B or Class A Signaling Line Circuit
devices.
NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2
Page 17