10.7 Dew Prevention Control
To prevent dew formation at indoor unit discharge area, the horizontal air vane is automatically set at position 2
(refer to 9.6).
This control is activated when following conditions are fulfilled:-
Compressor runs continuously for 60 minutes.
Horizontal air vane is at position 4 or 5 (refer to 9.6).
Actual fan speed is lower than Lo level.
Intake air temperature is lower than 29℃
Intake air temperature changes within 2℃ for more than 30 minutes.
This control stopped if anyone of the following conditions is achieved:-
Any of the above condition is out of the range described above.
Operation stops.
Power OFF.