Table 35. GPU thermal restrictions configuration (continued)
PowerEdge R640 2.5 inch hard drives x 10 x2GPU
TDP(Watts)
Thermal restriction
165 W Gold 6146
performance heat sink
150 W 6144 and 6244
150 W Gold 6240Y
70 to 165 W
NOTE:
PowerEdge R640 does not support x3 GPU T4 (PPGXG) in 2.5 inch x10 hard drive chassis.
Ambient temperature limitations
The following table lists configurations that require ambient temperature less than 35°C.
NOTE:
The ambient temperature limit must be adhered to ensure proper cooling and to avoid excess processor
throttling, which may impact system performance.
Table 36. Configuration based ambient temperature restrictions
System
Front Backplane
PowerEdge R640
10 x 2.5 inch SAS/
SATA hard drives
8 x 2.5 inch SAS/
SATA hard drives
4 x 3.5 inch SAS/
SATA hard drives
10 x 2.5 inch SAS/
SATA and NVMe
drives(4, 8, or 10)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 37. Particulate contamination specifications
Particulate contamination
Air filtration
in slot 1,3
Thermal restriction at 35
o
at 30
C
required
High performance
fans and standard
heat sink required
Processor Thermal
Design Power
200 W, 205 W
165 W
200 W, 205 W
Thermal restriction
o
C
performance heat sink
Not supported
Processor Heat
Sink
2 pipe 1U high
performance
2 pipe 1U standard
2 pipe 1U high
performance
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a
95% upper confidence limit.
NOTE:
This condition applies to data center environments only.
Air filtration requirements do not apply to IT equipment designed
to be used outside a data center, in environments such as an
office or factory floor.
NOTE:
Air entering the data center must have the MERV11 or
MERV13 filtration.
PowerEdge R640 (2.5 inch hard drives x 8
x3GPU)
Thermal restriction at
o
at 30
C
required
High performance
fans and standard
heat sink required
Fan Type
High performance
fan
High performance
fan
Technical specifications
o
35
C
Not supported
Ambient
Restriction
30°C
30°C
41