Toshiba RAV-SM182UTP-UL Installation Manual page 23

Hide thumbs Also See for RAV-SM182UTP-UL:
Table of Contents

Advertisement

[Procedure example]
Manual address setup procedure
While the operation stops, change the setup.
(Stop the operation of the unit.)
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the "Field setting menu".
Push and hold the buttons for more than 4
seconds.
Push the [
˄ ] / [
˅ ] button to select
"DN setting" on the "Field setting menu"
screen, then push the "
Set"
[
F2] button.
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
Select the group-controlled function on the
menu screen, then push the "
[
F2] button.
Push the "
unit" [
F1] button to
select the unit to set.
The selected unit changes as follows each
time the button is pushed:
Push the "
Set" [
F2] button.
The setting display for the selected unit
appears.
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
43-EN
(* Display changes according to
the model No. of indoor unit.)
2
The indoor UNIT No. in the group control is
displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of
which setup is changed can be confirmed
because fan of the selected indoor unit operate.
3
1. Specify CODE No. [12] with Move the cursor to
select "Code(DN)" with the "
[
F1] button, then set "Code(DN)" with the
[
˄ ] / [
˅ ] button.
(CODE No. [12]: Line address)
2. Change the line address from [3] to [2] with
Move the cursor to select "Data" with the
"
>" [
F2] button, then set "Data"
with the [
˄ ] / [
˅ ] button.
3. Push the [
MENU] button to set the other
Code (DN) and Data. After "Continue?" is
displayed on the screen, push the
"
Yes" [
F1] button.
Set"
Indoor UNIT No. before setup change is displayed.
4
1. Specify CODE No. [13] with Move the cursor to
select "Code(DN)" with the "
[
F1] button, then set "Code(DN)" with the
[
˄ ] / [
˅ ] button.
(CODE No. [13]: Indoor address)
2. Change the Indoor address from [3] to [2] with
Move the cursor to select "Data" with the
"
>" [
F2] button, then set "Data"
with the [
˄ ] / [
˅ ] button.
3. Push the [
MENU] button to set the other
Code (DN) and Data. After "Continue?" is
displayed on the screen, push the
"
Yes" [
F1] button.
Indoor UNIT No. before setup change is displayed.
5
1. Specify CODE No. [14] with Move the cursor to
select "Code(DN)" with the "
[
F1] button, then set "Code(DN)" with the
[
˄ ] / [
˅ ] button.
(CODE No. [14]: Group address)
<"
2. Change the SET DATA from [0001] to [0002] with
Move the cursor to select "Data" with the
"
>" [
F2] button, then set "Data"
with the [
˄ ] / [
(SET DATA [Header unit: 0001] [Follower unit:
0002])
3. Push the [
MENU] button to set the other
Code (DN) and Data. After "Continue?" is
displayed on the screen, push the
"
Yes" [
Indoor UNIT No. before setup change is displayed.
<"
6
If there is other indoor unit to be changed,
2
repeat procedure
setup.
When the above setup has finished, push
Select the group-controlled function on the
menu screen, then push the "
[
F2] button.
� 22 �
Push the "
select the unit to set.
The selected unit changes as follows each
time the button is pushed:
Push the "
The setting display for the selected unit
appears.
before change of setup, specify CODE No. [12],
[13], [14] in order with Move the cursor to
select "Code(DN)" with the "
[
F1] button, then set "Code(DN)" with the
[
˄ ] / [
changed contents.
Address change check Before change:
<"
[3-3-1] → After change: [2-2-2]
The contents of which
setup was changed.
(In this case, procedure from
Indoor UNIT No. before setup change is displayed.
˅ ] button.
F1] button.
5
to
to change the
Set"
unit" [
F1] button to
Set" [
F2] button.
<"
˅ ] button. and then check the
2
is repeated.)
EN
44-EN

Advertisement

Table of Contents
loading

Table of Contents