Drain Piping - Toshiba RAV-SM182UTP-UL Installation Manual

Hide thumbs Also See for RAV-SM182UTP-UL:
Table of Contents

Advertisement

 Installation of ceiling panel
(Sold separately)
Install the ceiling panel according to Installation
Manual attached with it after piping / wiring work has
completed.
Check that installation of indoor unit and ceiling
opening part is correct, and then install it.
REQUIREMENT
• Joint the connecting sections of ceiling panel, ceiling
surface, ceiling panel and indoor unit closely.
Any gap between them will cause air leakage and
the generate condensation or water leakage.
• Remove the adjust corner caps at the four corners
of the ceiling panel, and then install the ceiling
panel onto the indoor unit.
• Make sure that the claws of the four adjust corner
caps are securely fit.
* Improper fitting of the claws may cause water
leakage.
 Installation of remote
controller (Sold separately)
For installation of the wired remote controller, follow the
Installation Manual attached with the remote controller.
• Pull out the remote controller cord together with the
refrigerant pipe or drain pipe.
Be sure to pass the remote controller cord through
upper side of the refrigerant pipe and drain pipe.
• Do not leave the remote controller at a place
exposed to the direct sunlight and near a stove.
 Wireless type
The sensor of indoor unit with wireless remote
controller can receive a signal by distance within
approx. 26'2" (8 m). Based upon it, determine a place
where the remote controller is operated and the
installation place.
• Operate the remote controller, confirm that the indoor
unit receives a signal surely, and then install it.
• Keep 3'3" (1 m) or more from the devices such as
television, stereo, etc.
(Disturbance of image or noise may generate.)
• To prevent a malfunction, select a place where is not
influenced by a fluorescent light or direct sunlight.
• Two or more (Up to 6 units) indoor units with wireless
type remote controller can be installed in the same
room.
21-EN
Signal receiving unit
26'2" (8 m)
 Installation of Electrical
cover 2 holes
REQUIREMENT
• In case of group control, electrical cover 1 hole type
need to change to electrical cover 2 holes type.
1. Remove screw A for the fixation of the electrical
control box cover and loosened screw B.
Slide the cover inside so that the hook part can be
removed (The electrical control box cover remain
being hooked on the hinge.)
2. Remove the wiring cover mounting screws
(1 locations), and a wiring cover is removed.
Screws B
Screws A
Hinge
Screws
Hook section
Cover of the electrical
Wiring cover
control box
3. Remove screw for the fixation of the wire box.
Screws
� 11 �
4. Remove screw 4 locations for the fixation cover pipe
and a cover pipe removed.
Screws
5. Remove electrical cover 1 hole and insert electrical
cover 2 holes from accessory on the pipe cover and
then screw it with original screw.
(Electrical cover 1 hole)
(Electrical cover 2 holes)
5

Drain piping

CAUTION
Following the Installation Manual, perform the
drain piping work so that water is properly
drained, and apply a heat insulation so as not to
cause a dew dropping.
Inappropriate piping work may result in water
leakage in the room and wet of furniture.
 Piping / Heat insulating
material
Screws
Require the following materials for piping and heat
insulating at site.
Hard vinyl chloride pipe VP25
Piping
(Outer dia. : Ø1.3" (32 mm))
Foam polyethylene :
Heat insulator
Thickness 0.4" (10 mm) or more
 Flexible hose
Use the attached flexible hose to adjust center
discrepancy of the hard vinyl chloride pipe or to adjust
the angle.
• Do not use the flexible hose as stretched, or do not
deform it more extent than that in the following figure.
• Be sure to fix the soft end of the flexible hose with the
attached hose band.
• Use the flexible hose on a horizontal level.
OK
NO GOOD
max
45°
max
45°
REQUIREMENT
• Be sure to perform heat insulation of the drain pipes
of the indoor unit.
• Never forget to perform heat insulation of the
connecting part with the indoor unit.
An incomplete heat insulation causes dew dropping.
• Set the drain pipe with downward slope (1/100 or
more), and do not make swelling or trap on the piping.
It may cause an abnormal sound.
4'9" to 6'7"
(1.5 to 2 m)
Support
bracket
1/100 or more
Heat insulator
downward
Riser (Trap)
90° Bend
22-EN