Toshiba RAV-SM182UTP-UL Installation Manual page 16

Hide thumbs Also See for RAV-SM182UTP-UL:
Table of Contents

Advertisement

 Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 3.9"(100 mm)) on a wire to hang down the electrical control box at servicing or other
purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
1. Remove the cover of the electrical control box by taking off the mounting screws (2 positions) and
pushing the hooking section. (The cover of the electrical control box remains hanged to the hinge.)
2. Connect the system interconnection wires and remote controller wire to the terminal block of the
electrical control box.
3. Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical
control box.
(Do not apply tension to the connecting section of the terminal block.)
4. Using the attached heat insulation material, seal the pipe connecting port. Otherwise, dewing may be
caused.
5. Mount the cover of the electrical control box without pinching wires.
(Mount the cover after wiring on the ceiling panel.)
 Heat insulation to wiring
connecting port
Adhered surface
Notched section
Power supply terminal block
L1 L2 S
Cord clamp
29-EN
Screws (2 positions)
Hinge
Louver connector
(CN510:White)
Side D (Space: 0.33"(8.5 mm))
Side C (Space: 0.15" (4 mm))
Select side C or D for the power cable clamping
position referring to the following table according to
Remote
the cable type and diameter.
controller
* Cable clamp can be attached on either right or left
terminal block
side.
When twin system are connected, clamp two cables
with one cable clamp.
Cable clamping
Wire type
Specification
position
Cabtyre
3-core stranded
cable
wire AWG14
Cabtyre
3-core stranded
cable
wire AWG16
� 15 �
0.4"(10 mm)
2.75"(70 mm)
Earth wire
 Remote controller wiring
Strip off approx. 0.35"(9 mm) the wire to be connected.
Wiring diagram
 Wiring on the ceiling panel
As per the Installation Manual of the ceiling panel, connect the connector (20P: White) of the ceiling panel to the
connector (CN510: White) onto the P.C. board within the electrical control box.
Side D
Side C
L1 L2
S
0.4"(10 mm)
1.97"(50 mm)
System interconnection wires
System interconnection wires
Terminal block for
remote controller
wiring of indoor unit
A
B
Remote controller wire
(Locally procured)
See the figure on the left for
system interconnection wires to
the terminal block.
Terminal block
Remote
A
controller
B
unit
30-EN