The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Schedule 40 Pipe
Pipe
Inside Diameter
Length
Natural
0-10ft
1/2"
0-3m
12.7mm
11-40ft
1/2"
4-12m
12.7mm
41-100ft
1/2"
13-30m
12.7mm
101-150ft
3/4"
31-46m
19mm
NotICE: Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
NotICE: Since some municipalities have additional local codes, it
is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The Commonwealth of Massachusetts requires
that a flexible appliance connector cannot exceed three feet in length.
FLEXIBLE GAS LINE CONNECTION
FLEX TUBING
FLARE FITTING
Gas Supply Pressure (inches w.c.)
Minimum
Natural Gas
Propane Gas
Natural Gas
Propane Gas
*Note: Remote "RF" Models - 10.5" w.c. maximum
Page 12

GAS SUPPLY

tubing, type L
outside Diameter
Propane
Natural
Propane
3/8"
1/2"
9.5mm
12.7mm
1/2"
5/8"
12.7mm
15.9mm
12.7mm
1/2"
3/4"
12.7mm
19mm
12.7mm
1/2"
7/8"
12.7mm
22.2mm
TEE HANDLE
FLARE SHUT
GAS SUPPLY
OFF VALVE
Figure 8
Normal
Maximum
4.5"
7.0"
10.8"
11.0"
Manifold Pressure (inches w.c.)
Normal (HI)
3.5"
10.0"
Installing a New Main Gas Shut-off
Each appliance should have its own manual gas shut-off.
A manual main gas shut-off should be located in the vicinity of the
unit. Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
3/8"
9.5mm
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
1/2"
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
1/2"
NotICE: The millivolt gas controls are equipped with a captured
screw type pressure test point, therefore it is not necessary to
3/4"
provide a 1/8" test point up stream of the control.
1.9 mm
On direct ignition valves, hex plugs may be replaced with hose fittings
for pressure checks, then reinstalled before operating fireplace.
When using copper or flex connector use only approved fittings.
The appliance and it's individual shut-off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
If one of the procedures results in pressures in excess of
1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will
result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural Gas valves have a built-in pressure
regulator in the gas valve. Natural Gas models will have a manifold
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5" w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa). Propane Gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8" w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0" w.c. (3.484kPa).
*14.0"
*14.0"
CAUtIoN
GAS LINE HOLE
(BOTH SIDES)
2"
10"
FROM FRONT OF
APPLIANCE TO
GAS LINE HOLE
Figure 9