Samsung MIM-B18 User Manual page 63

Data management server2, bacnet gateway, lonworks gateway for air conditioner
Hide thumbs Also See for MIM-B18:
Table of Contents

Advertisement

Setting the Inspection Section
1
Click [EHP Power Consumption Inspection]
inspection section] when DMS2 web page menu screen
appears.
2
Click [Edit] when inspection result screen appears.
 1 section is set as default.
3
Select a section and enter time by section.
 You should enter time of section B when selecting
section. And you should enter time if section B and C
when selecting 3 sections.
 Correct format of time is HH:MM.
Ex) 4:30 in the afternoon
4
Click [Save].
 Set power section will be saved in DMS2.
 If you do not click [Save], changed setting will not be
saved.
Note
 Ex) When selecting 2 sections(A, B, C)
If the border time between A and B is 08:00, section A is
00:00 ~ 08:00,
section B is 08:01 ~ 18:00, and section A again is
18:01 ~ 24:00.
 Checking inspection result by section is available in
S-NET 3 only.
 [Setting the
 16:30
63
E-