Angled Wall Radiation Shield - Superior Fireplaces WRT4820 Installation And Operation Instruction Manual

Table of Contents

Advertisement

Support
Straps
NOTE: This illustration is not to scale. It represents how the chimney
must be supported. A 30 degree offset only is allowed in the USA
and a 45 degree maximum offset is allowed in Canada.
Figure 34 - Offset Chimney Installation
Rain Cap
Framing
2" x 3"
NOTE: In cold areas it is recommended to
Figure 35
protect the chimney in a insulated chase.
ACRS
Straps
Chimney AC
Starter Section
*
Collar
Roof Flashing
Offset Support
Insulated Wall
Radiation Shield
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

ANGLED WALL RADIATION SHIELD

When traversing a combustible wall with the chimney at a 30º or 45º
angle, an angled firestop or wall radiation shield must be installed. Only
one is required.
NOTE: 45º angle for Canada only (
In cold climate locations (climates where temperatures will fall below 32°
F / 0° C), we recommend that you use the insulated wall radiation shield
since it will maintain the home's thermal barrier.
Security Chimneys
®
RSM+ and RSMI30
(RSMI45 - Canada Only)
Chimney Model
Angle
30º
ASHT / HT6103+ (6" dia).
Canada only
45º
30º
DuraTech DTC **
(6" dia). Canada only
45º
30º
S-2100+ / HT6000+ / AC
(6" dia).
30º
Table 5
Insulated Wall
Drywall
Figure 36
*
RSMI45
/ 6DTC-S45)
*
DuraVent
®
6DTC-WTI and 6DTC-S30
(6DTC-S45 - Canada Only)
Hole Size
283 mm x 781 mm (11-1/8" x 30-3/4")
283 mm x 518 mm (11-1/8" x 20-3/8")
283 mm x 781 mm (11-1/8" x 30-3/4")
283 mm x 518 mm (11-1/8" x 20-3/8")
327 mm x 881 mm (12-7/8" x 34-11/16")
380 mm x 972 mm (15" x 38-1/4")
Insulated Wall
Radiation Shield*
Available from Security Chimneys
*
21
®