End Position Guiding - Samson 5827 Mounting And Operating Instructions

Hide thumbs Also See for 5827:
Table of Contents

Advertisement

The error message is reset and the actuator returns to closed-loop operation if the input sig-
nal moves within 0.2 V or 0.4 mA of the lower range value.
Settings\Actuator\Functions
Functions
Detect input signal failure
Positioning value upon input signal failure
Internal positioning value

16.3.2 End position guiding

The actuator stem moves to the end position earlier if the end position guiding function is
active.
− 'Value below limit (end position guiding)'
The actuator stem moves to the 0 % position when the input signal falls below 'Value
below limit (end position guiding)'.
− 'Value above limit (end position guiding)'
The actuator stem moves to the 100 % position when the input signal falls below 'Value
above limit (end position guiding)'.
Note
When 'Value below limit (end position guiding)' = 0 % and 'Value above limit (end position
guiding)' = 100 %, the end position guiding function is deactivated.
Settings\Actuator\Functions
Functions
Value below limit (end position guiding)
Value above limit (end position guiding)
EB 5827-2 EN
Annex A (configuration instructions)
WE
Adjustment range
No
Yes/No
Internal
Internal, last position
0.0 %
0.0 to 100.0 %
WE
Adjustment range
1.0 %
0.0 to 49.9 %
97.0 %
50.0 to 100.0 %
16-3

Advertisement

Table of Contents
loading

Table of Contents