2-3. How to connect program timer
2-4. Names and functions
<PAC-SC32PT>
WEEKLY TIMER SETTING DISPLAY
Used for selection of if or not the day opera-
tion pattern set by PATTERN SETTING is to
be applied in weekly day unit,
setting.
SET/MONITOR DISPLAY
During SET is display, clock adjustment,
change of weekly day, daily and weekly timer
setting can be performed.
During MONITOR is display, all switches
except SET/MONITOR SW are invalidated.
This is normal status.
WEEK DAY SETTING SW
Used for week day setting.
MODE SELECTOR SW
Using this switch select "MONITOR" or "SET"
Mode.
"MONITOR" :Indicates the current timer set-
ting. All switch expect MODE
SELECTOR SW are invalidated
then.This is the normal status.
"SET": Set to "SET" mode for clock adjust-
ment, charge of week day, daily and
weekly timer setting.
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page
59.
Part No.
ORN
BRN
RED
56
CURRENT TIME DISPLAY
During MONITOR status, cur-
rent time is display.
During Daily timer setting,a time
desire for timer setting is dis-
played.
S M T W T F S
SET
MONITOR
SET/MONITOR
TODAY
CLOCK
PROERAN TIMER
PAC-SC32PTA
CLOCK ADJUSTMENT SW
Used for adjustment of the current time.
Push
SW to advance the time. Each time the button is
pushed the time advance by 1 minute, pushing continuously
advances by 1 minute at 0.5 second interval, and when the
lower digit of minute becomes 0 indication advances in 10 min-
utes unit.
SW is used for reversing the time. Each time the button is
pushed the time reverses by 1 minute, pushing continuously
reverses the time by 1 minute at 0.5 second interval, and when
the lower digit of minute becomes 0 indication reverses in 10
minutes unit.
PAC-SA89TA-E
1
2
3
SET BACK DISPLAY
Indicates the setting set
back range.
SET
BACK
0
3
6
12
15
12
15
18
21
24
WEEKLY
DAILY
SETTING
SET BACK
ON
SETTING
ON
SET BACK
OFF
OFF
DAILY TIMER
DAILY TIMER SETTING DISPLAY
24 hours is divided into 48 blocks and each
block express 30 minutes.
The block display consists of 3 pattern.
Set back can be done in the range of 1,2,4,6
and 8°C.
SET BACK SETTING SW
Used for set back setting.
ON/SET BACK/OFF SW
Used to specify the time setting pattern.
DAILY TIMER SW
Used for timer setting in 30 minutes unit.
WEEKLY TIMER SW
Used for setting timer in day of week unit.
Pushing
SW moves the week day light
display in order of
W ...
S
M
T
enabling to set the week day.