OPERATING PROCEDURE
4. Removing the fan
Note : Perform the following with the indoor unit lowered
down to the floor.
(1) Remove the drain pan.
(2) Disconnect the connector for the fan motor.
(3) Take out the fan assembly after removing the 7 set
screws of the fan plate.
(4) Unscrew four set screws of the bell mouth and remove it.
(5) Loosen the set screw of the fan to pull out the sirocco
fan.
(6) Unscrew the four set screws of the motor fittings, and
remove the fan motor.
Photo 7
Bell mouth
Set screw
5. Removing the heater
(1) Remove the drain pan.
(2) Disconnect the connector of the heater.
(3) Unscrew the set screw of the heater.
(4) Pull out the heater.
Photo 9
Set screw (for heater)
50
(See Photo 1.)
(See Photo 3.)
(See Photo 5 or 6.)
(See Photo 7.)
(See Photo 7.)
(See Photo 8.)
Fan casing
Sirocco fan
Fan plate
Fixture set screw
(See Photo 1.)
(See Photo 9.)
Heater
PHOTOS
Photo 5
Set screw
Photo 6
Fan casing
Photo 8
Fixture set screw
Fittings
Fan plate
Fan motor
Fan plate
Set screw
Fan motor