DRY OPERATION
w11
Refer to page 26~27.
w12
When room temperature is 18: or below, the compressor cannot operate.
When room temperature rises over 18:, the compressor starts after a 3-minute time delay.
w13
Compressor ON time is decided by room temperature. Refer to page 26~27.
w14
In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
22
DRY
operation
Four-way valve / OFF
YES
Room tempereature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
NO
Compressor &
thermostat ON
YES
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w12
NO
NO
w11
YES
NO
w14
YES
3-minute
time delay
NO
w11
Compressor &
thermostat
ON
NO
10-minute
NO
compressor
OFF
YES
w13
Compressor ON
time set
Compressor ON
w14
Fan speed LOW