Siemens SIMATIC RTU3041C Manual page 63

Securely connecting and monitoring to telecontrol server basic
Hide thumbs Also See for SIMATIC RTU3041C:
Table of Contents

Advertisement

2 Engineering
9. Open the Data points tab.
10. Set the following settings for the digital input "float (DI0)":
Transmission method: (Event (only current values))
Trigger: Change
Transfer mode: Buffered transfer
11. Set the following settings for the digital input "enableReadFillLevel (DI1)":
Transmission method: (Event (only current values))
Trigger: Change
Transfer mode: Buffered transfer
12. Set the following settings for the digital input "gpsPosition (DM2)":
Transmission method: (Event (only current values))
Trigger: Change
Transfer mode: Buffered transfer
13. Set the following settings for the digital memory bit "critFillLevel (DM1)":
Transmission method: (Event (only current values))
Trigger: Change
Transfer mode: Unsolicited transfer
14. Set the following settings for the analog input "fillLevel (AI0)":
Transmission method: (Event (only current values))
Trigger: Change
Threshold (%): 5.00
Transfer mode: Buffered transfer
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240,
V3.0,
07/2021
63