Siemens SIMATIC RTU3041C Manual page 42

Securely connecting and monitoring to telecontrol server basic
Hide thumbs Also See for SIMATIC RTU3041C:
Table of Contents

Advertisement

2 Engineering
30. Select the measurement type of your analog level sensor. The SITRANS
Probe LU150 sensor must be set to "Current (2-wire connector)".
31. Enter the settling and integration time as well as the smoothing of the signal of
your sensor. The following settings are recommended for the SITRANS Probe
LU150 sensor:
Settling time: 30,000 ms
Integration time: 40 ms
Smoothing: Weak
Note
Note that (settling time + integration time) * smoothing factor must not be longer
than the update mode cycle.
32. Enter the sensor and process values for your application. In this application
example, a sensor signal of 20 mA corresponds to a level of 10,000 m³.
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240,
V3.0,
31
07/2021
30
42

Advertisement

Table of Contents
loading

Table of Contents