Toshiba nv Series Instruction Manual page 67

Devicenet module
Hide thumbs Also See for nv Series:
Table of Contents

Advertisement

For details on how to use the DeviceNet configurator tool, refer to the ACM manual.
This chapter describes about simple operation method for registering DeviceNet slave I / O devices using ACM.
If the screen or setting method changes due to ACM version upgrade, etc., refer to the ACM instruction manual.
This chapter uses the following diagram as an example of the configuration.
I/O Node No = 03h
RP913
Receiving block (High speed)
Receiving block (Mid-speed)
RAS information
Sending block (High speed)
Sending block (Mid-speed)
Figure 4-5 Example of system configuration using DN912 and its settings
■DN912 module parameter
High-speed scan use byte size (Output): 128
High-speed scan use byte size (Input): 128
Bit strobe output speed: Medium speed
Controller input data at the time of error: Previous value retained
■DeviceNet node address = 1
RAS information
1794-ADN
[1]
DeviceNet
Input Address
= 0 to 1
0
128
IB16 input
Input area
output area (High speed)
OB16 output
Unified Controller nv Series DeviceNet Module DN912 Instruction Manual
Allen-Bradley Flex I/O node address = 3
1794-IB16
[2]
Input Address
= 2 to 5
756 bytes polling bit strobe
Input area
756 bytes polling output area
12 bytes (reserve)
8-byte bit strobe output area
4.4 DeviceNet network setting
1794-IB16
[3]
Output Address
=0 to 3
51