Hydraulic Systems; Priming The Pump - Riello 40 F20 Installation, Use And Maintenance Instructions

Oil burner
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 15

HYDRAULIC SYSTEMS

WARNING : Before starting the burner make sure that the return pipe-line is not clogged: any ob-
struction would cause the pump seals to break.
Important : The pump is supplied for use with a two pipe system.
For use on a one pipe system, it is necessary to remove
the by-pass screw (A), (see figure).
D5374
H = Difference of level.
L = Max. length of the suc-
tion line.
I.D. = Internal diameter of the
oil pipes.
D5376
A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe.
ONLY FOR ITALY: Automatic shut-off device as per Ministry of Internal Affairs' regulation
2095
L meters
H
ø
meters
8 mm
0
35
0.5
30
1
25
1.5
20
2
15
3
8
3.5
6
no. 73 dated 7/29/71.
L meters
H
ø
i
meters
8 mm
0,5
10
1
20
1,5
40
2
60
The pump vacuum should not exceed
ø
i
i
a maximum of 0.4 bar (30 cm Hg).
10 mm
Beyond this limit gas is released from
100
the oil.
100
Oil lines must be completely airtight.
100
90
The return line should terminate in
70
the oil tank at the same level as the
30
suction line; in this case a non-return
20
valve is not required.
When the return line arrives over the
fuel level, a non-return valve must be
used.
This solution however is less safe than
previous one, due to the possibility of
leakage of the valve.

PRIMING THE PUMP:

Start the burner and wait for the prim-
ing. Should lock-out occur prior to the
arrival of the fuel, await at least 20 sec-
onds before repeating the operation.
3
GB
ø
i
10 mm
20
40
A
80
100
D5199

Advertisement

Table of Contents
loading

This manual is also suitable for:

3452782

Table of Contents