9. OPTIONS AND PERIPHERAL EQUIPMENT
9.5 FR-CV-H power regenerative common converter
When using FR-CV-H with MR-J4-_A4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC27] to "_ _ _ 1". When
using it with MR-J4-_B4(-RJ), set [Pr. PA02] to "_ _ 0 1" and set [Pr. PC20] to "_ _ _ 1".
(1) Model
(2) Selection
FR-CV-H power regenerative common converter can be used for the servo amplifier of 11 kW to 22 kW.
The following shows the restrictions on using the FR-CV-H.
(a) Up to two servo amplifiers can be connected to one FR-CV-H.
(b) FR-CV-H capacity [W] ≥ Total of rated capacities [W] × 2 of servo amplifiers connected to FR-CV-H.
(c) The total of used servo motor rated currents should be equal to or less than the applicable current
[A] of the FR-CV-H.
(d) Among the servo amplifiers connected to the FR-CV-H, the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].
The following table lists the restrictions.
POINT
For details of the power regenerative common converter FR-CV-H, refer to the
FR-CV Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L1, L2, and L3)
of the servo amplifier. Doing so will fail the servo amplifier and FR-CV-H.
Connect the DC power supply between the FR-CV-H and servo amplifier with
correct polarity. Connection with incorrect polarity will fail the FR-CV-H and
servo amplifier.
Two or more FR-CV-H's cannot be installed to improve regeneration capability.
Two or more FR-CV-H's cannot be connected to the same DC power supply
line.
When using FR-CV-H, set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
Maximum number of connected servo
amplifiers
Total of connectable servo amplifier
capacities [kW]
Total of connectable servo motor rated
currents [A]
Maximum servo amplifier capacity [kW]
Capacity
Symbol
Capacity [kW]
22K
22
30K
30
37K
37
55K
55
Symbol
Voltage class
H
400 V class
Item
9 - 34
FR-CV-H_
22K
30K
37K
1
11
15
18.5
43
57
71
11
15
15
55K
2
27.5
110
22