Installation of 20/40/60 Minute Timer (435247)

Installation Requirements
The following installation requirements must be followed:
Timers mount in standard 2 x 4" (51 x 102 mm) electrical boxes.
If multiple timers are used, individually wire each timer to the unit.
Use 3-wire 20−gauge (min.) low−voltage wire.
Lockout Mode
The timer can be set to lockout mode (timers disabled) as follows: press and hold the
button for five seconds; the status lights will flash; then release the button. The timer
is now in lockout mode.
If the button is pressed during lockout mode, the status lights will momentarily
illuminate but no override will be initiated. If lockout mode is initiated when the timer
is activated, the timer will continue its timed sequence but will not allow any further
overrides to be initiated.
To unlock lockout mode, press and the button for five seconds; until the high-speed
status lights stop flashing; then release the button. The timer will now operate
normally.

Installation of Third Party Mechanical Timers

The ERV is compatible with two wire, "dry contact" third party mechanical timers. This
may be useful for retrofit situations where only two wires are available for the timer.
Install the two wire timer by connection a jumper wire between ON and RED. Connect
the two timer wires to ON and HI.
NOTE: An alternative to using the 2-wire timers is to install the system with wireless
timers.

Interlocking ERV to Air Handler/Furnace Blower

Connecting the ERV unit as illustrated will ensure the air handler/furnace
blower motor is operating whenever the ERV is ventilating.
The ERV unit must be interlocked to the furnace/air handler with a simplified
(return/return) installation and a partially dedicated installation as illustrated in
the following figure.
Note: Terminal Block "Type A" displayed in figures, refer to "Terminal Blocks"
on page 21.
24
Residential Energy Recovery Ventilators
20/40/60 Minute
Status Lights
Select Button
Figure 32. 20/40/60 Minute Timer
Connect the two wires from the timer
to ON and HI on the terminal block
LOW
1
6
HI
ON
2
7
COM
RED
3
8
NO
YE L
4
9
NC
2-wire timers
GRN
5
10
require a jumper
BLK
between ON and
RED on the
terminal block
Caution: Low Voltage Only
Figure 33. Dry Contacts Connections
CAUTION: Low Voltage Only
LOW
1
6
HI
ON
2
7
COM
Wire
RED
3
connection
8
NO
YEL
4
9
NC
GRN
5
10
BLK
R
G W Y C
Furnace or air handler
Figure 34. Air Handler/Furnace Blower Connections
TERMINAL BLOCK Connections
(From timer to terminal block)
Yellow on timer to YELLOW #4
Red on timer to RED #3
Green on timer to GREEN #5
YEL
RED
GRN
LOW
1
6
HI
ON
2
7
COM
RED
RED
3
8
NO
YEL
YEL
4
9
NC
GRN
GRN
5
10
BLK
Caution: Low Voltage Only
OFF
10
20
60
30
50
40
Thermostat