Typical Installation

WARNING
Installation and troubleshooting to be performed only
by qualified person(s).
WARNING
Use only GFCI receptacles.
Not for outdoor applications.
AVERTISSEMENT
La pose et le dépannage ne doivent être effectués que
par des personnes qualifiées.
AVERTISSEMENT
Utiliser uniquement des prises comportant un
disjoncteur différentiel (GFCI).
Ne pas utiliser à l'extérieur.
IMPORTANT: Only mount fan to building structure.
1. Remove the fan from its packaging.
2. Using a 3/8 inch socket, loosen the lower bolts on
both sides of the fan's handle so that the handle is
able to pivot from side to side. Position the handle
at the desired mounting angle, then re-tighten the
bolts.
3. Using a 9/16 inch deep well socket, attach the
eyebolt to the top of the fan handle.
EYEBOLT
NUT
WASHER
NYLOCK NUT
FACTORY WIRED,
3 CONDUCTOR CORD
(115V, SINGLE PHASE)
SPEED CONTROLLER
HOUSING ASSEMBLY
®
4. Attach the beam clamp assembly to the ceiling
7. Wrap the loose end of the factory-installed safety
IMPORTANT: Safety restraint cable must be installed
for proper function of the fan. Failure to install the safety
retention cable will result in voiding of the fan warranty.
8. Secure the safety restraint cable to the mounting
EYEBOLT
HANDLE
NOTE: Safety restraint cable will only feed through
the Gripple connector in one direction (marked on the
Gripple connector with an arrow). If necessary, the
SAFETY CABLE
safety cable can be loosened by pressing the release
structure. Use the quick connect link to mount
the handle eyebolt on the fan to the beam clamp
assembly.
BEAM CLAMP ASSEMBLY
HANDLE EYEBOLT
restraint cable around the mounting structure so
that the cable is installed 45º to 60º from vertical.
Do not allow the cable to come in contact with any
sharp edges.
structure using the provided No. 2 Gripple
connector. Pull the loose end of the cable through
the Gripple connector to tighten the cable. The
cable should be pulled taut, leaving only a small
amount of slack to ensure proper functioning.
45°-60°
1.
Directional Destratification Fans
QUICK CONNECT
2.
3.
3