Terminal Blocks

Figure 27. Type A
The ASSURE-120S-S1, SYNC-110SE-S1 and SYNC-270TCE-S1
have a terminal block Type A as shown in Figure 27.

Installation of Controls

The Two-Speed Controls may either be installed onto a flush mounted electrical
switch box or surface mounted onto the wall. The optional PrecisionSYNC
Control (435244) is to be surface mounted onto a wall. Only one control can be
installed with a ventilation system.
1.
For the PrecisionSYNC Control (435244), remove the operating instructions
card from the top of the control (Figure 29, Box A).
2.
Separate the face plate from the back plate by firmly pulling apart (Figure 29,
Boxes B or C). Be careful not to damage face plate contact pins.
3.
For the PrecisionSYNC Control, place the back plate of the control in the
desired location on the wall and pencil mark the wall with the right and left
screw holes (Figure 29, Box D).
4.
For the Two-Speed Switch with Humidity Sensor (435245) and Two-Speed
Switch with Intermittent Mode (435246), place the back plate of the control
in the desired location on the wall and pencil mark the top and bottom
screw holes (Figure 29, Boxes E or F). For mounting the control without a
decorative plate, break off top and bottom tabs and refer to Figure 29, Box F
for mounting.
5.
Remove the back plate from the wall and mark the center hole for the wires
in the middle of the screw holes. Refer to Figure 29, Boxes D, E or F for
dimensions.
6.
Drill (two) 1/8" (3 mm) holes for the screws and wall anchors (Figure 29,
Boxes D, E or F). For the PrecisionSYNC Control , drill a one inch hole in the
center (Figure 29, Box D). For the Two-Speed Switch with Humidity Sensor
(435245) and Two-Speed Switch with Intermittent Mode (435246), cut in a
3/4" (19 mm) by 1" (25 mm) oval hole in the center (Figure 29, Boxes E or F).
7.
Pull 3-wire 20 gauge (minimum) 100 feet (30-1/2 meters) length (maximum),
through the opening in the wall.
8.
Connect red, green, and yellow to the wiring terminals located on the back plate (Figure 29, Boxes D, E or F).
9.
Attach the back plate to the wall using two supplied screws and anchors.
10. Attach the face plate to the back plate (Figure 29, Boxes B or C).
NOTE: Be careful to correctly align the face plate to avoid damaging the face plate contact pins.
11. For the PrecisionSYNC Control (435244), insert the instructions card into the control (Figure 29, Box A).
12. Connect the 3-wire 20 gauge (minimum) 100 feet (30-1/2 meters) length (maximum to the terminal block located on ventilator
(Red, Yellow, and Green).
13. On the terminal block connect a jumper wire between ON and RED. Refer to "Installing Standby Jumper" on page 25.
Pay special attention not to damage the contact pins when removing and detaching the face plate.
®
The SYNC-180SCE-S1 has a terminal block Type B as shown in
IMPORTANT
H
L
ON
R
Y
G
Top View
C
NO NC DH
Figure 28. Type B
Figure 28.
Operating
Instruction Card
BOX A
BOX B
BOX C
Back Plate
Front Plate
Keep top / bottom
vent openings cleared
1/8" (3 mm) hole
for screw and
anchor
1/8" (3 mm) hole
1.625"
for screw and
(41 mm)
0.75" (19 mm)
1' x 3/4"
(25 mm x 19 mm)
oval hole for
(25 mm x 19 mm)
wire opening
1 "
wire opening
Wiring
1.625"
Te rminals
(41 mm)
1/8" (3 mm) hole
for screw and
anchor
BOX E
Figure 29. Installation of Controls
Residential Energy Recovery Ventilators
Face Plate
Back Plate
Keep top / bottom
vent openings cleared
Two 1/8" (3 mm) holes
for screws and anchors
1" (25 mm) hole
Wiring
for wire opening
Te rminals
BOX D
Break o tab
anchor
1' x 3/4"
Wire hole
0.75 " (19 mm)
centered
oval hole for
between
1 "
screw holes
Wiring
Te rminals
1/8" (3 mm) hole
for screw and
Break o tab
anchor
BOX F
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sync-110se-s1Sync-180sce-s1Sync-270tce-s1

Table of Contents