Minimum Spacing Requirements; Mechanical Installation Mounting Installation; Universal Mounting Kit - Greenheck AMPLIFY DM Installation, Operation And Maintenance Manual

Overhead ceiling fans
Table of Contents

Advertisement

Minimum Spacing Requirements

3 FT. CLEARANCE AROUND BLADES
A
Fan Size (ft.)
5
Mechanical Installation
Mounting Installation
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
DANGER
Pour écarter les risques d'incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l'installation ou l'entretien.

Universal Mounting Kit

IMPORTANT: Structural Engineer of Record (SEOR)
must perform thorough evaluation of mounting structure
and determine final mounting requirements before fan
is installed. Manufacturer is not liable for any problems
that arise as the result of insufficient structure, including
(but not limited to) vibration, noise, or safety hazards.
Product warranty will be voided at manufacturer's
discretion if structure is deemed insufficient.
®
3 FT. CLEARANCE AROUND BLADES
B
Minimum Spacing From Center of Fan (ft.)
Fan Diameter (in.)
A
60
7.5
Installations must comply with the following
requirements at a minimum, but SEOR may require
more stringent specifications at their discretion:
Required Loose Components (Included):
Hardware/Tools Needed (Not Included):
C
B
15
 Fans must be directly secured to structural
member(s) that are an existing part of the building
such as joists/trusses or beams. Do not install fan
so that it is only supported by ceiling sheathing.
• Universal Mounting Yoke (1)
• Mounting Hardware, Specified By Others
1. Identify desired mounting location for fan on
structural member(s) that are an existing part of
the building. The Structural Engineer of Record
(SEOR) must perform a thorough evaluation of
the mounting structure and determine all final
mounting requirements before the fan is installed.
It is the sole responsibility of the installer to ensure
that the mounting structure and fan installation
method are adequate for safe operation of the fan.
HVAC
DIFFUSER
2X FAN DIAMETER
FROM HVAC
WHEN FULL DIFFUSER OUTLET
IS BELOW FAN,
FAN MUST BE 1X FAN DIAMETER AWAY
C
7
Overhead Ceiling Fans
7