Mounting The Control - Bosch rexroth ctrlX CORE Operating Manual

Hide thumbs Also See for rexroth ctrlX CORE:
Table of Contents

Advertisement

26 / 50

Mounting the control

The cabling of the Ethernet wires may not leave the building.
Use strain reliefs for all cables and place them the closest possible to the connection of the control.
Install the control only horizontally on a support rail attached to a wall.
Keep the maximum possible distance from interference sources.
Provide the following minimum distances for sufficient cooling:
In case of a several line design, the supply air has to be measured under each line and its limit value
has to be observed. For information on ambient temperatures, refer to
conditions of the ctrlX CORE" on page
35 mm
0 mm
35 mm
35 mm
Fig. 9: Minimum distances for the circulation of ambient air
Additionally, provide sufficient distance for mounting, dismounting, plugs and cables.
10.3
Mounting the control
NOTICE
NOTICE
Bosch Rexroth AG
12.
0 mm
0 mm
Damage of the device by plug mounting under voltage!
Before mounting or dismounting components, disconnect the control -
including its components - from voltage.
Connect the voltage only after the control and its components have been
set up.
Possible damage to property due to unintended mounting of the support rail
Fasten the support rail adequately.
Connect the support rail to a functional ground.
Mount the control on the support rail, as the support rail is also used for
heat dissipation and grounding.
Install the control in a control cabinet or an appropriate housing.
ctrlX CORE
⮫ Chapter 6.1 "Ambient
35 mm
35 mm
35 mm
R911405645, Edition 05
0 mm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth ctrlx corex-cRexroth ctrlx corex-m

Table of Contents