Bosch rexroth ctrlX CORE Operating Manual page 22

Hide thumbs Also See for rexroth ctrlX CORE:
Table of Contents

Advertisement

22 / 50
Interface description
Process data of the bus coupler
The bus coupler has data that is inserted into the cyclic process image. This data length is 5 words
in total. According to the Ethercat standard, this data before the input process data is shown in the
process image.
The process data words 0...3 contain the voltage and current values of U
consumption of the infeed terminal and the I/O modules) as well as their bits for the supply voltage
diagnostics of the bus coupler. This information can also be retrieved via acyclic services using CoE.
These are shown as the indices 6000, 6010 and 6020 hex.
Word 0
Word 1
Word 2
Word 3
Word 4
0
1
2
3
4
5
6-15
Diagnostic strategy
Mechanisms
Different mechanisms are used for the diagnostics of the bus coupler.
Mechanism
Ethercat state machine
Ethercat hardware watchdog
Diagnostic objects in the CoE object directory
10F1
Diagnosis history object
10F3
For the status codes of the "Ethercat state machine" and the diagnostic codes across all
modules, refer to .
Bosch Rexroth AG
U
Voltage
P
U
Current
P
U
Voltage
L
U
Current
L
(Only the current consumption of the infeed terminal (typ. 50 mA) and the
I/O modules (3 A max.) is measured. In addition to the transferred measured
value (typ. 350 mA), the ctrlX CORE and the multi-Ethernet unit consume
more than shown here.
U
Undervoltage
P
U
Overvoltage
P
U
Overcurrent
P
U
Undervoltage
L
U
Overvoltage
L
U
Overcurrent
L
Reserved
Diagnostics
Ethercat system diagnostics
Extended diagnostics, e.g. periphery errors
Error settings
20 diagnostic messages can be stored
Diagnosis history
ctrlX CORE
and U
(only the current
P
L
R911405645, Edition 05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth ctrlx corex-cRexroth ctrlx corex-m

Table of Contents