Fujitsu Waterstage Split Comfort 5 Series Installation Manual page 59

Air/water heat pump split 2 services
Table of Contents

Advertisement

Line
Function
5813
S
Output el imm heater K26
Without electrical backup = 0 ; Single phase electrical backup 3 kW = 0 ;
Single phase electrical backup 6 kW (Factory setting) = 3 ; 3-phase electrical backup = 0
5950
S
Function input H1 (Connector X86, terminals B1 & M)
0: None, 1: Op'mode change zones+DHW, 2: Optg mode changeover DHW, 3: Op'mode changeover zones,
4: Op'mode changeover zone 1, 5: Op'mode changeover zone 2, 6: Op'mode changeover zone 3,
8: Error/alarm message, 9: Consumer request VK1, 10: Consumer request VK2, 11: Release swi pool source heat,
13: Release swi pool solar, 14: Operating level DHW, 15: Operating level HC1, 16: Operating level HC2,
17: Operating level HC3, 18: Room thermostat HC1, 19: Room thermostat HC2, 20: Room thermostat HC3,
21: DHW fl ow switch, 24: Pulse count, 26: Dewpoint monitor, 27: Flow temp setp incr hygro, 30: Swi-on command HP stage 1,
35: Status info suppl source, 36: Charg prio DHW sol fuel boil, 43: Ventilation switch 1, 44: Ventilation switch 2,
45: Ventilation switch 3, 50: Flow measurement Hz, 51: Consumer request VK1 10V, 52: Consumer request VK2 10V,
54: Pressure measurement 10V, 55: Humidity measurement 10V, 56: Room temp 10V, 59: Flow measurement 10V,
60: Temp measurement 10V, 61: Air quality measurement 10V
5953
S
Input value 1 H1
5954
S
Function value 1 H1
5955
S
Input value 2 H1
5956
S
Function value 2 H1
5960
S
Function input H3 (Connector X86, terminals B2 & M)
0: None, 1: Op'mode change zones+DHW, 2: Optg mode changeover DHW, 3: Op'mode changeover zones,
4: Op'mode changeover zone 1, 5: Op'mode changeover zone 2, 6: Op'mode changeover zone 3,
8: Error/alarm message, 9: Consumer request VK1, 10: Consumer request VK2, 11: Release swi pool source heat,
13: Release swi pool solar, 14: Operating level DHW, 15: Operating level HC1, 16: Operating level HC2,
17: Operating level HC3, 18: Room thermostat HC1, 19: Room thermostat HC2, 20: Room thermostat HC3,
21: DHW fl ow switch, 24: Pulse count, 26: Dewpoint monitor, 27: Flow temp setp incr hygro, 30: Swi-on command HP stage 1,
35: Status info suppl source, 36: Charg prio DHW sol fuel boil, 43: Ventilation switch 1, 44: Ventilation switch 2,
45: Ventilation switch 3, 50: Flow measurement Hz, 51: Consumer request VK1 10V, 52: Consumer request VK2 10V,
54: Pressure measurement 10V, 55: Humidity measurement 10V, 56: Room temp 10V, 59: Flow measurement 10V,
60: Temp measurement 10V, 61: Air quality measurement 10V
5963
S
Input value 1 H3
5964
S
Function value 1 H3
5965
S
Input value 2 H3
5966
S
Function value 2 H3
5980
S
Function input EX1
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push.
5981
S
Contact type input EX1
5982
S
Function input EX2
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push.
5983
S
Contact type input EX2
5985
S
Contact type input EX3
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN
Setting range
or display
0.1-...99
0...1000
-100.. 500
0... 1000
-100... 500
0...1000
-100.. 500
0... 1000
-100... 500
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
Setting
Basic
increment
setting
3 kW
None
0
0
10
100
None
0
0
10
100
Electrical
utility lock E6
NO
Low-tariff E5
NC
NO
- 59 -