Fujitsu Waterstage Split Comfort 5 Series Installation Manual page 54

Air/water heat pump split 2 services
Table of Contents

Advertisement

Line
Function
1150
I
Floor curing function
- Off : Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends automatically
after 25 days.
1151
I
Floor curing setpoint manually
(if line 1150 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains fi xed.
The concrete slab-drying program stops automatically after running for 25 days.
1156
I
Floor curing day current
1157
I
Floor curing day completed
1200
S
Operating mode changeover
Operating mode at end of concrete slab drying period.
Cooling circuit 2
If the installation is fi tted with the cooling kit (Only with the cooling kit option).
1201
U
Operating mode
1202
U
Comfort cooling setpoint
1203
U
Reduced setpoint
1208
I
Flow temp setp at OT° 25°C
1209
I
Flow temp setp at OT° 35°C
1212
I
Cooling limit at OT°
1213
S
Lock time at end of heating / cooling
1218
S
Summer comp start at OT°
1219
S
Summer comp end at OT°
1220
S
Summer comp setp increase
1223
S
Flow temp setp min OT° 25°C
1224
S
Flow temp setp min OT° 35°C
1228
S
Room infl uence
If the installation is fi tted with a room thermostat:
This function enables you to choose the ambient temperature's infl uence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1232
S
Room temp limitation
1238
S
Mixing valve decrease
1241
S
Actuator running time
1263
S
With primary controller / system pump
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
- 54 -
(fi g. 51, page
52)
Setting range
or display
0... 95 °C
0... 32
0... 32
None, Protection mode,
Reduced, Comfort, Automatic
Protection, Automatic, Reduced,
Comfort
17... 40 °C
5... 40°C
6... 35 °C
6... 35 °C
--, 8... 35 °C
--, 8... 100
20... 50 °C
20... 50 °C
--, 1... 10 °C
6... 35 °C
6... 35 °C
--, 1... 100 %
--, 0.5... 4 °C
0... 20 °C
30... 650 s
No, Yes
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN
Setting
Basic
increment
setting
Off
1 °C
25 °C
0
0
Reduced
Protection
0.5 °C
24 °C
0.5 °C
26 °C
0.5 °C
20 °C
0.5 °C
16 °C
0.5 °C
24 °C
1 h
24 h
1 °C
26 °C
1 °C
40 °C
1 °C
4 °C
0.5 °C
18 °C
0.5 °C
18 °C
1 %
80 %
0.5 °C
0.5 °C
1 °C
0 °C
1 s
240 s
No*