Technical Data

6.4 Electrical Tests

High-energy surge voltages
IEC 61000-4-5, installation class 3
Auxiliary voltage
Relay output (Life Contact)
Communication interfaces
High-energy surge voltages
TBR14 (3), ETS 300046-3 Sect. 5.7.1
Communication interfaces
Conducted HF, amplitude-modulated
IEC 61000-4-6, class III
Conducted HF, amplitude-modulated
Spot frequencies
IEC 61000-4-6
Power frequency magnetic field immunity test
IEC 61000-4-8, class IV
IEC 60255-6
Oscillatory surge withstand capability
IEEE Std C37.90.1
Radiated electromagnetic interference
IEEE Std C37.90.2
Damped oscillatory wave immunity test
IEC 61000-4-18
EMC Electromagnetic Emission Tests (Type Test)
STANDARD
Conducted emission on lines
IEC-CISPR22
Radiated emission
IEC-CISPR22
Voltage variations and flicker on the network lead at
AC 230 V
IEC 61000-3-3
40
Pulse: 1.2/50 μs
Common mode: 2 kV; 12 Ω; 9 μF
Differential mode: 1 kV; 2 Ω; 18 μF
Common mode: 2 kV; 42 Ω; 0.5 μF
Common mode: 2 kV; 2 Ω; 18 μF
Common mode: 2 kV; 15 Ω; 18 μF
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
10 V; 27 MHz and 68 MHz
30 A/m, continuously; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
2.5 kV (peak value); 1 MHz; τ = 15 ms;
400 impulses per s; test duration 2 s; R
35 V/m; 80 MHz to 1000 MHz
2.5 kV (peak value), alternating polarity
100 kHz, 1 MHz, R
EN 61000-6-3 (generic standard)
150 kHz to 30 MHz
Limit class B
30 MHz to 1000 MHz
Limit class B
Limits are observed
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
= 200 Ω
i
= 200 Ω
i
C53000-B1174-C190-1, Edition 01.2022