Samsung AM AXV Series Installation Manual page 19

Table of Contents

Advertisement

H/R
33.6 kW 40.0 kW
61.6 kW
(2)
(A)
(1)
(C)
(B)
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
*Maximum pipe length within
90m
Outdoor unit
capacity (kW)
Low
Liquid
(Cooling)
pressure
(mm)
gas (mm)
Capacity ≤ 25
Ø 19.05
Ø 9.52
25 < Capacity ≤ 32
Ø 22.22
32 < Capacity ≤ 39
39 < Capacity ≤ 44
Ø 12.70
44 < Capacity ≤ 48
Ø 28.58
48 < Capacity ≤ 55
55 < Capacity ≤ 66
Ø 15.88
66 < Capacity ≤ 72
Ø 34.92
72 < Capacity ≤ 100
100 < Capacity ≤ 139
Ø 19.05
Ø 41.28
139 < Capacity ≤ 173
173 < Capacity ≤ 252
Ø 22.22
Ø 53.98
252 < Capacity
Ø 25.40
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
※ For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
※ For the case that the diameter of the default pipe of an outdoor unit does not match that of
the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
※ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe
connected to the outdoor unit (A), apply the pipe size (A).
Branch pipe length within 45m
Indoor unit
Low
Liquid
capacity (kW)
pressure
(mm)
gas (mm)
Capacity ≤ 15
Ø 15.88
15 < Capacity ≤ 25
Ø 9.52
Ø 19.05
25 < Capacity ≤ 32
Ø 22.22
32 < Capacity ≤ 39
39 < Capacity ≤ 44
Ø 12.70
44 < Capacity ≤ 48
Ø 28.58
48 < Capacity ≤ 55
55 < Capacity ≤ 66
Ø 15.88
66 < Capacity ≤ 72
Ø 34.92
72 < Capacity ≤ 100
100 < Capacity ≤ 139
Ø 19.05
Ø 41.28
139 < Capacity ≤ 173
173 < Capacity ≤ 252
Ø 22.22
Ø 53.98
252 < Capacity
Ø 25.40
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
(D)
(F)
(3)
(E)
*Maximum pipe length over 90m
High
Low
High
Liquid
pressure
pressure
pressure
(mm)
gas (mm)
gas (mm)
gas (mm)
Ø 15.88
Ø 22.22
Ø 15.88
Ø 12.70
Ø 25.40
note1)
Ø 19.05
Ø 19.05
Ø 28.58
Ø 15.88
Ø 22.22
Ø 22.22
Ø 31.75
note2)
Ø 19.05
Ø 28.58
Ø 28.58
Ø 38.10
note3)
Ø 22.22
Ø 41.28
Ø 34.92
Ø 34.92
Ø 53.98
Ø 41.28 Ø 25.40
note1)
Ø 41.28
Ø 44.45
Ø 28.58
Ø 44.45
Branch pipe length between 45~90m
High
Low
High
Liquid
pressure
pressure
pressure
(mm)
gas (mm)
gas (mm)
gas (mm)
Ø 19.05
Ø 15.88
Ø 15.88
Ø 12.70
Ø 22.22
Ø 25.40
note1)
Ø 19.05
Ø 19.05
Ø 28.58
Ø 15.88
Ø 22.22
Ø 22.22
Ø 31.75
note2)
Ø 19.05
Ø 28.58
Ø 28.58
Ø 38.10
note3)
Ø 22.22
Ø 41.28
Ø 34.92
Ø 34.92
Ø 53.98
Ø 41.28 Ø 25.40
note1)
Ø 41.28
Ø 44.45
Ø 28.58
Ø 44.45
Ex.) 135.2 kW
Capacity (kW)
No.
Liquid
33.6
(1)
Ø 12.70
Ø 19.05
73.6
(2)
Ø 19.05
135.2
(3)
Size of the pipe between the branch joint and the indoor unit (F)
Make a selection according to outdoor unit capacity.
Indoor unit capacity
(kW)
Liquid
6.0 and below
Ø 6.35
6.1 ~ 16.0
Ø 9.52
16.1 ~ 23.0
Ø 9.52
Ø 9.52
Over 23.0
Branch joint
Branch joint between outdoor units (C)
Classification
Model name
MXJ-TA3419M
Liquid/Low pressure
Y-joint (C)
MXJ-TA4122M
MXJ-TA3100M
High pressure
Y-joint (C)
MXJ-TA3800M
First branch joint (D)
Make a selection according to outdoor unit capacity.
Classification
Model name of the branch joint
MXJ-YA1509M
MXJ-YA2512M
MXJ-YA2812M
Liquid/Low pressure
MXJ-YA2815M
Y-joint (D)
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
MXJ-YA1500M
MXJ-YA2500M
High pressure Y-Joint
(D)
MXJ-YA3100M
MXJ-YA3800M
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected
after the branch.
※ However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe
connected to the outdoor unit (D), apply the pipe size (D)
• Y-joint
Classification
Model name
MXJ-YA1509M
MXJ-YA2512M
MXJ-YA2812M
Y-joint (E)
MXJ-YA2815M
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
MXJ-YA1500M
MXJ-YA2500M
Y-joint (E)
(Only H/R)
MXJ-YA3100M
MXJ-YA3800M
Pipe size (mm)
Gas
Ø 28.58
Ø 34.92
Ø 41.28
Pipe size (O.D. mm)
Gas
Ø 12.70
Ø 15.88
Ø 19.05
Ø 22.22
Specification (kW)
135.2 and below
Over 135.2
135.2 and below
Over 135.2
Outdoor unit capacity (kW)
15.0 and below
15.1 ~ 40.0
40.1 ~ 45.0
45.1 ~ 70.3
70.4 ~ 98.4
98.5 ~ 135.2
Over 135.2
22.4 and below
22.5 ~ 70.3
70.4 ~ 135.2
Over 135.2
Specification (kW)
15.0 and below
15.1 ~ 40.0
40.1 ~ 45.0
45.1 ~ 70.3
70.4 ~ 98.4
98.5 ~ 135.2
Over 135.2
22.4 and below
22.5 ~ 70.3
70.4 ~ 135.2
Over 135.2