Samsung AM AXV Series Installation Manual page 17

Table of Contents

Advertisement

H/P
33.6 kW 40.0 kW
(A)
(1)
(B)
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit
*Maximum pipe length within 90m *Maximum pipe length over 90m
capacity (kW)
(Cooling)
Liquid (mm)
Capacity ≤ 25
Ø 9.52
25 < Capacity ≤ 32
32 < Capacity ≤ 39
39 < Capacity ≤ 44
Ø 12.70
44 < Capacity ≤ 48
48 < Capacity ≤ 55
55 < Capacity ≤ 66
Ø 15.88
66 < Capacity ≤ 72
72 < Capacity ≤ 100
100 < Capacity ≤ 139
Ø 19.05
139 < Capacity ≤ 173
173 < Capacity ≤ 252
Ø 22.22
252 < Capacity
Ø 25.40
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor
unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
※ For the case that the diameter of the default pipe of an outdoor unit does not match that of
the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after
the branch.
※ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe
connected to the outdoor unit (A), apply the pipe size (A).
Branch pipe length within 45m
Indoor unit
capacity (kW)
Liquid (mm)
Capacity ≤ 15
15 < Capacity ≤ 25
Ø 9.52
25 < Capacity ≤ 32
32 < Capacity ≤ 39
39 < Capacity ≤ 44
Ø 12.70
44 < Capacity ≤ 48
48 < Capacity ≤ 55
55 < Capacity ≤ 66
Ø 15.88
66 < Capacity ≤ 72
72 < Capacity ≤ 100
100 < Capacity ≤ 139
Ø 19.05
139 < Capacity ≤ 173
173 < Capacity ≤ 252
Ø 22.22
252 < Capacity
Ø 25.40
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
61.6 kW
(D)
(3)
(2)
(E)
(C)
Gas (mm)
Liquid (mm)
Gas (mm)
Ø 19.05
Ø 22.22
Ø 12.70
Ø 22.22
Ø 25.40
Ø 28.58
Ø 15.88
Ø 28.58
Ø 31.75
note2)
Ø 19.05
Ø 34.92
Ø 38.10
Ø 22.22
Ø 41.28
Ø 41.28
Ø 53.98
Ø 25.40
note1)
Ø 53.98
Ø 28.58
Branch pipe length between
45~90m
Gas (mm)
Liquid (mm)
Gas (mm)
Ø 19.05
Ø 15.88
Ø 19.05
Ø 12.70
Ø 22.22
Ø 22.22
Ø 25.40
Ø 28.58
Ø 15.88
Ø 28.58
note2)
Ø 31.75
Ø 19.05
Ø 34.92
Ø 38.10
Ø 22.22
Ø 41.28
Ø 41.28
Ø 53.98
note1)
Ø 25.40
Ø 53.98
Ø 28.58
Ex.) 135.2 kW
Capacity (kW)
No.
33.6
(1)
73.6
(2)
135.2
(3)
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
Indoor unit capacity
(kW)
6.0 and below
6.1 ~ 16.0
note1)
16.1 ~ 23.0
Over 23.0
Branch joint between outdoor units (C)
Classification
note3)
Y-joint for outdoor
unit (C)
First branch joint (D)
Make a selection according to outdoor unit capacity.
Classification
Model name of the branch joint
Y-joint (D)
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected
after the branch.
※ However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe
connected to the outdoor unit (D), apply the pipe size (D).
1) Y-joint
Classification
note1)
Y-joint (E)
2) Distribution header
Classification
note3)
Distribution header (E)
Pipe size (mm)
Liquid
Gas
Ø 12.70
Ø 28.58
Ø 19.05
Ø 34.92
Ø 19.05
Ø 41.28
Pipe size (O.D. mm)
Liquid
Gas
Ø 6.35
Ø 12.70
Ø 9.52
Ø 15.88
Ø 9.52
Ø 19.05
Ø 9.52
Ø 22.22
Branch joint
Model name
Specification (kW)
MXJ-TA3419M
135.2 and below
MXJ-TA4122M
Over 135.2
Outdoor unit capacity (kW)
MXJ-YA1509M
15.0 and below
15.1 ~ 40.0
MXJ-YA2512M
40.1 ~ 45.0
MXJ-YA2812M
45.1 ~ 70.3
MXJ-YA2815M
MXJ-YA3419M
70.4 ~ 98.4
MXJ-YA4119M
98.5 ~ 135.2
MXJ-YA4422M
Over 135.2
Model name
Specification (kW)
MXJ-YA1509M
15.0 and below
15.1 ~ 40.0
MXJ-YA2512M
40.1 ~ 45.0
MXJ-YA2812M
45.1 ~ 70.3
MXJ-YA2815M
MXJ-YA3419M
70.4 ~ 98.4
MXJ-YA4119M
98.5 ~ 135.2
MXJ-YA4422M
Over 135.2
Model name
Specification (kW)
MXJ-HA2512M
45.0 and below (for 4 rooms)
MXJ-HA3115M
70.3 and below (for 8 rooms)
MXJ-HA3819M
70.4 ~ 135.2
17
English

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents