Samsung AM AXV Series Installation Manual page 33

Table of Contents

Advertisement

Installing the branch joints
Branch joints must be installed 'horizontally' or 'vertically' .
Horizontal installation
Vertical installation
NOTE
• For A~J type branch joints : Connect the branch joint to the
connection pipe with the provided reducer.
• For K~Z type branch joints : Cut the connection part of the
branch joint or the provided socket, according to the diameter
of the connection pipe, before connecting them.
CAUTION
• Install the branch joint within ±15° of the horizon or vertical line.
• Make sure that the pipe is not bent at where it is connected to
the branch joint.
• Keep a minimum straight line distance of 500mm or more
before connecting branch joint.
After branching
Socket
Pipe
Gas side/Liquid side branch joint
Connect to
Before branching
indoor unit
※ Install within ±15° of the horizon or vertical line.
Over 10~15mm
Connect to other
branch joint or
indoor unit
Pipe connection
Socket
After branching
Minimum
straight line
(over 500mm)
Installing the distribution header
1 Select the reducer that fits the diameter of the pipe.
Pipe*
To outdoor unit
Socket
<Liquid side>
Pipe*
To outdoor unit
Socket
<Gas side>
※ Pipe : Separately purchased item
2 If the number of connected indoor unit is fewer than ports on
the distribution header, block the unused ports with caps.
Welding part Provided item
Connect in
order
Install indoor units from largest to
smallest capacity, starting at the inlet of
the header.
<Liquid side>
Connect in
order
Install indoor units from largest to
smallest capacity, starting at the inlet of
the header.
<Gas side>
NOTE
• For A~J type distribution header :
Connect the distribution header to the connection pipe with
the provided reducer.
• For K~Z type distribution headers :
Cut the provided socket, according to the diameter of the
connection pipe, before connecting it.
Provided item
Socket
Pipe*
To indoor unit
Socket
Pipe *
To indoor unit
Connect in
order
Install
Case of blocking the unused distribution
header ports.
* Keep unused port from ① to avoid oil trap.
Connect in
order
Install
Case of blocking the unused distribution
header ports.
* Keep unused port from ① to avoid oil trap.
Over 10~15mm
English
33