Setting outdoor unit option switch and key function
K2 (Number of press)
1 time
2 times
3 times
4 times
H/P: Automatic setting of operation mode (Cooling/Heating)
5 times
6 times
7 times
8 times
9 times
10 times
11 times
12 times
13 times
14 times
15 times
16 times
※ Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since they are charged with
high DC voltage.
※ When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/repairing them. (Wait for
more than 15 minutes to allow it to discharge naturally.)
※ When there were error, 'Discharge mode of DC link voltage' may not have been effective. Especially if error E464 and E364 have been
occurred, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link voltage' .
※ During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
※ If the voltage does not drop during 'Discharge mode of DC link voltage' , please cut-off the power and wait for 15 minutes until voltage
discharges naturally. Due to the characteristics of the inverter PCB, 'Discharge mode of DC link voltage' may not be supported.
※ When pressing K2 key 9 to 12 times without inverter checker, error code can be displayed on segment even though the outdoor unit is normal.
※ If error have been occurred, do not use the key operation.
※ If the 1st-generation MCU is installed, the Auto pipe pairing operation can not be used.
If the 2nd-generation MCU is installed, the Checking the pipe connection can not be used.
– 1st-generation MCU : MCU-S*NEE*N, MCU-S2NEK1N
– 2nd-generation MCU : MCU-S*NEK2N,MCU-S4NEK3N,MCU-S1NEK1N
※ KEY operation of K2 15 times(Automatic refrigerant charging fuction) is an unused function.
It can be available with Automatic refrigerant charging option KIT.
K3 (Number of press)
1 time
K4 (Number of press)
1 time
2 times
3 times
4 times
5 times
6 times
7 times
8 times
9 times
58
English
KEY operation
Refrigerant charging in Cooling mode
Trial operation in Cooling mode
Pump down all units in Cooling mode
H/R: Checking the pipe connection
for trial operation
Checking the amount of refrigerant
Discharge mode of DC link voltage
Forced defrost operation
Forced oil collection
Inverter compressor 1 check
Inverter compressor 2 check
Fan 1 check
Fan 2 check
H/R : Auto pipe pairing
H/P : Unused
Baseheater testing mode
Unused
End Key operation
KEY operation
Initialize (Reset) setting
KEY operation
Capacity of Outdoor unit Model
Order frequency of the compressor 1
Order frequency of the compressor 2
High pressure (MPa)
Low pressure (MPa)
Discharge temperature (Compressor 1)
Discharge temperature (Compressor 2)
IPM temperature (Compressor 1)
IPM temperature (Compressor 2)
Display on segment
"K" "5" "BLANK" "BLANK"
"K" "6" "BLANK" "BLANK"
"K" "7" "BLANK" "BLANK"
"K" "8" "BLANK" "BLANK"
"K" "9" X X (Display of last two digits may differ depending on
the progress)
"K" "A" "BLANK" "BLANK"
"K" "B" "BLANK" "BLANK"
"K" "C" "BLANK" "BLANK"
"K" "D" "BLANK" "BLANK"
"K" "E" "BLANK" "BLANK"
"K" "F" "BLANK" "BLANK"
"K" "G" "BLANK" "BLANK"
"K" "H" X X (Display of last two digits may differ depending on
the progress)
"K" "I" "BLANK" "BLANK"
"K" "J" "BLANK" "BLANK"
-
Display on segment
Same as initial state
Display on segment
SEG 1
SEG2, 3, 4
AM160AXV*** → Off, 1, 6
1
120 Hz → 1, 2, 0
2
120 Hz → 1, 2, 0
3
1.52 MPa → 1, 5, 2
4
0.43 MPa → 0, 4, 3
5
87 °C → 0, 8, 7
6
87 °C → 0, 8, 7
7
87 °C → 0, 8, 7
8
9
87 °C → 0, 8, 7