Figure 7.
Rear view of D-Frame AFDH cabinet with dimensions
2
1.
Motor terminal access cover. Size of cutout is 8 in. x 16.5 in.
2.
Centerline of Z-bracket mounting studs
3.
UCP2™ or CH531 / Tracer® AdaptiView™ control box
4.
Center-to-center spacing of the mounting notches for the angle iron bracket clips that will be removed from the unit mounted starter being
replaced and reused.
Drive Unit Mount Weights and
Heat Rejection
Table 5.
AFDH D-Frame unit weights (460 V/480 V)
460 V/V480 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 6.
AFDH D-Frame unit weights (380 V/400 V)
380 V/400 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 7.
AFDH D-Frame unit weights (575 V/600 V)
575 V/600 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
AFDH-SVN03H-EN
1
4
281 Catalog/
301 Maximum
675 lb
14,300 Btu/hBtu/h
293 Catalog/
315 Maximum
675 lb
14,300 Btu/h
178 Catalog/
226 Catalog/
192 Maximum
242 Maximum
675 lb
11,262 Btu/h
14,300 Btu/h
AFDH Drive Package Specifications
336 Catalog/
413 Catalog/
361 Maximum
443 Maximum
700 lb
16,380 Btu/h
367 Catalog/
446 Catalog/
395 Maximum
480 Maximum
700 lb
16,380 Btu/h
271 Catalog/
2905 Maximum
700 lb
775 lb
16,380 Btu/h
500 Catalog/
535 Maximum
775 lb
1100 lb
19,800 Btu/h
24,450 Btu/h
545 Catalog/
588 Maximum
775 lb
1100 lb
19,800 Btu/h
24,450 Btu/h
321 Catalog/
374 Catalog/
344 Maximum
400 Maximum
1100 lb
19,800 Btu/h
24,450 Btu/h
1100 lb