Micropilot FMR20 HART About this document About this document Document function These Operating Instructions provide all of the information that is required in various phases of the life cycle of the device including: • Product identification • Incoming acceptance • Storage •...
For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate 1.3.1 Technical Information (TI)
Android, Google Play and the Google Play logo are trademarks of Google Inc. Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Endress+Hauser...
‣ With regard to special media and media used for cleaning, please contact the manufacturer. Endress+Hauser will be happy to assist in clarifying the corrosion- resistant properties of wetted materials but does not accept any warranty or liability. Residual risks...
Micropilot FMR20 HART Basic safety instructions Workplace safety For work on and with the device: ‣ Wear the required personal protective equipment according to federal/national regulations. Operational safety Risk of injury! ‣ Operate the device only if it is in proper technical condition, free from errors and faults.
Basic safety instructions Micropilot FMR20 HART IT security We only provide a warranty if the device is installed and used as described in the Operating Instructions. The device is equipped with security mechanisms to protect it against any inadvertent changes to the device settings.
‣ Enter the serial number from the nameplate into the Endress+Hauser Operations App or use the Endress+Hauser Operations App to scan the 2-D matrix code (QR Code) provided on the nameplate All the information about the measuring device and the scope of the associated Technical Documentation are displayed.
Micropilot FMR20 HART Incoming acceptance and product identification Nameplate Order code: Ser. no.: Ext. ord. cd.: MWP: Tp max: DeviceID: Dev.Rev.: ex works Mat.: if modification see sep. label Date: A0029096 2 Nameplate of Micropilot Manufacturer address Device name Order code Serial number (Ser.
Micropilot FMR20 HART Installation A0046282 4 Nozzle installation The maximum nozzle length L depends on the nozzle diameter D. Please note the limits for the diameter and length of the nozzle. 80 mm (3 in) antenna, installation inside nozzle •...
Installation Micropilot FMR20 HART • Avoid measurements through the filling curtain. • Avoid internal fixtures such as limit switches. • No signals are evaluated within the Blocking distance (BD). It can therefore be used to suppress interference signals (e.g. the effects of condensate) in the vicinity of the antenna.
Micropilot FMR20 HART Installation A0045325 7 Aligning the sensor with the product cone Installation with adjustable flange seal Installation with FAU40 alignment unit To avoid disturbance echoes, use metal plates installed at an angle (where necessary) 5.1.5 Beam angle α...
• Please ensure there are no interfering installations made of a conductive material in the signal beam (see the beam angle section for information on calculating the beamwidth diameter). For more information: contact the Endress+Hauser sales organization. 5.1.7 Weather protection cover A weather protection cover is recommended for outdoor use.
Micropilot FMR20 HART Installation A0046286 10 Weather protection cover The sensor is not completely covered by the weather protection cover. 5.1.8 Use of flooding protection tube In free-field installations and/or in applications where there is a risk of flooding, the flooding protection tube must be used.
Installation Micropilot FMR20 HART ensures a defined detection of the maximum level directly at the end of the tube. Due to the fact that the Blocking distance is inside the tube, multiple echoes are not analyzed. Configuration parameters for flooding protection tube Configuring the blocking distance when using the flooding protection tube ‣...
Micropilot FMR20 HART Installation A0045327 13 Cantilever installation, with pivot Cantilever with wall bracket Cantilever with mounting frame Cantilever, pivotable 5.1.11 Installation with the horizontal mounting bracket The mounting bracket can be ordered together with the device via the product structure "Accessory enclosed".
8° 8° A0045331 17 Micropilot FMR20 with adjustable flange seal Post-installation check Is the device or cable undamaged (visual inspection)? Is the device adequately protected from wet conditions and direct sunlight? Is the device properly secured?
The sensor' s Bluetooth® wireless technology communication can be disabled to increase the operating life of the battery. Potential equalization No special measures for potential equalization are required. Various power supply units can be ordered as an accessory from Endress+Hauser. Endress+Hauser...
Electrical connection Micropilot FMR20 HART Connecting the device 6.3.1 4 to 20 mA HART block diagram Connection of the device with HART communication, power source and 4 to 20 mA display A0028908 20 Block diagram of HART connection Device with HART communication...
Micropilot FMR20 HART Electrical connection 6.3.2 HART device block diagram, connection with RIA15 FMR20 with RIA15 (incl. option for FMR20 basic configuration) The RIA15 remote indicator can be ordered together with the device. Product structure, feature 620 "Accessory enclosed": • Option R4 "Remote indicator RIA15 non-hazardous area, field housing"...
Electrical connection Micropilot FMR20 HART 6.3.3 Block diagram of HART device, RIA15 with installed HART communication resistor module The HART communication module for installation in the RIA15 can be ordered together with the device. Product structure, feature 620 "Accessory enclosed": Option R6 "HART communication resistor hazardous / non-hazardous area"...
Page 27
Micropilot FMR20 HART Electrical connection Has the voltage drop across the process indicator and communication resistor been taken into account? Endress+Hauser...
Operability Micropilot FMR20 HART Operability Operating concept • 4 to 20 mA, HART • Menu guidance with brief explanations of the individual parameter functions in the operating tool • Optional: SmartBlue (app) via Bluetooth® wireless technology Operation via Bluetooth® wireless technology A0046293 ...
Micropilot FMR20 HART System integration via HART protocol System integration via HART protocol Overview of the device description files Manufacturer ID 17 (0x11) Device type ID 44 (0x112c) HART specification Measured variables via HART protocol The following measured values are assigned to the HART variables:...
Commissioning and operation Micropilot FMR20 HART Commissioning and operation Installation and function check Perform the post-installation check and the post-connection check prior to commissioning. 9.1.1 Post-installation check Is the device or cable undamaged (visual inspection)? Is the device adequately protected from wet conditions and direct sunlight? ...
Micropilot FMR20 HART Commissioning and operation 4. Enter the login data: User name: admin Password: serial number of the device 5. Tap the icons for more information. After logging in for the first time, change the password! 9.2.4 Envelope curve display in SmartBlue Envelope curves can be displayed and recorded in SmartBlue.
Commissioning and operation Micropilot FMR20 HART A0029487 29 Envelope curve display (sample) in SmartBlue for iOS Record video Create screenshot Display mapping menu Start/stop video recording Move time on time axis Operation and settings via RIA15 A0017719 30...
Micropilot FMR20 HART Commissioning and operation 9.3.1 Operating functions The operating functions of the process indicator are divided into the following menus. The individual parameters and settings are described in the "Commissioning" section. If the operating menu is disabled by means of a user code, the individual menus and parameters can be displayed but not changed.
Commissioning and operation Micropilot FMR20 HART As a general rule, the sensor is a slave and transmits information only if a request has been made by the master. A HART loop can have a maximum of two HART masters at any one time.
Page 35
Micropilot FMR20 HART Commissioning and operation Using the following operating matrix, a display in percent can be set. To do this, select "Mode" parameter => 4-20 and "Unit" parameter =>% MENU SETUP Parameters Values visible at Description MODE 4-20 Select the operating mode for the...
Micropilot FMR20 HART Commissioning and operation 9.4.2 Displaying level value as % With the combination of Full calibration and Empty calibration and with an output signal of 4 to 20 mA, the level value for 4 mA (=empty) and the level value for 20 mA (=full) can be determined directly in the unit of length used.
Commissioning and operation Micropilot FMR20 HART 9.5.3 Software locking via access code in SmartBlue The configuration data can be write-protected using an access code (software locking). ‣ Navigate to: Setup → Advanced setup → Administration → Administration1 → Define access code → Confirm access code The new access code must differ from the last access code used and may not be "0000".
Micropilot FMR20 HART Commissioning and operation 10 12 A0028411 32 Timeline for Bluetooth wireless technology recovery sequence, time in minutes 9.5.6 RIA15 locking The device setup can be locked with a 4-digit user code Additional information is available in the Operating Instructions for the RIA15...
Diagnostics and troubleshooting Micropilot FMR20 HART Diagnostics and troubleshooting 10.1 General errors Error Possible cause Solution Device does not respond Supply voltage does not match the Apply correct voltage specification on the nameplate The polarity of the supply voltage Correct the polarity...
Device cannot be Incorrect Enter correct password operated via password entered SmartBlue Device cannot be Password Contact the Endress+Hauser Service department operated via forgotten SmartBlue Device cannot be The sensor If the ambient temperature results in an elevated sensor operated via temperature is too temperature of >60 °C (140 °F), Bluetooth communication may be...
Diagnostics and troubleshooting Micropilot FMR20 HART 5. Press 3 times 6. Press The diagnostic event from the FMR20 is shown on the RIA15 display. 10.5 List of diagnostic events Diagnostic Short text Remedy instructions Status signal Diagnostic...
Micropilot FMR20 HART Maintenance Maintenance No special maintenance work is required. 11.1 Cleaning the antenna The antenna may become contaminated depending on the application. Emission and reception of microwaves can thus be potentially hindered. The level of contamination leading to an error depends on the medium and on the reflectivity, mainly determined by the dielectric constant ε...
12.1 General notes 12.1.1 Repair concept The Endress+Hauser repair concept is devised in such a way that repairs can only be carried out through device replacement. 12.1.2 Replacing a device After the device has been replaced, the parameters can be uploaded to the device via FieldCare/DeviceCare.
Micropilot FMR20 HART Accessories Accessories 13.1 Device-specific accessories 13.1.1 Weather protection cover The weather protection cover can be ordered together with the device via the product structure "Accessory enclosed". Ø 98 (3.86) A0046295 33 Dimensions of weather protection cover, engineering unit: mm (in)
Accessories Micropilot FMR20 HART 13.1.2 Flooding protection tube 80 mm (3 in) Suitable for use with devices with a 80 mm (3 in) antenna and "Mounting customer side w/o flange" process connection. The flooding protection tube can be ordered together with the device via the product structure "Accessory enclosed".
Micropilot FMR20 HART Accessories 13.1.3 Mounting bracket, adjustable The mounting bracket can be ordered together with the device via the product structure "Accessory enclosed". 92.5 (3.64) 70 (2.76) 12 (0.47) 9 (0.35) A0046296 35 Dimensions of mounting bracket, engineering unit: mm (in) Consists of: •...
Accessories Micropilot FMR20 HART 13.1.4 UNI flange 3"/DN80/80, PP The UNI flange 3"/DN80/80 can be ordered together with the device via the product structure "Accessory enclosed". 150 (5.91) 160 (6.3) 200 (7.87) A0037947 36 Dimensions of UNI flange 3"/DN80/80, engineering unit: mm (in) Sensor connection in accordance with product structure "Process connection on rear"...
Micropilot FMR20 HART Accessories 13.1.5 UNI flange 4"/DN100/100, PP The UNI flange 4"/DN100/100 can be ordered together with the device via the product structure "Accessory enclosed". 175 (6.89) 190.5 (7.5) 228.6 (9.0) A0037948 37 Dimensions of UNI flange 4"/DN100/100, engineering unit: mm (in) Sensor connection in accordance with product structure "Process connection on rear"...
Accessories Micropilot FMR20 HART 13.1.6 Cantilever, pivotable Sensor installation A0045347 38 Installation type sensor process connection rear side Installation with cantilever and wall bracket Installation with cantilever and mounting frame Cantilever Wall bracket Mounting frame Cantilever arm 500 mm, for G 1" or MNPT 1" connections on rear 585 (23) 35 (1.4)
Page 51
Micropilot FMR20 HART Accessories Cantilever arm 1 000 mm, for G 1" or MNPT 1" connections on rear 1085 (42.7) 35 (1.4) 300 (11.8) 75 (2.9) 75 (2.9) 100 (3.9) 750 (29.5) 35 (1.4) A0037807 40 Dimensions. Unit of measurement mm (in) Weight: 5.4 kg (11.91 lb)
Page 52
Accessories Micropilot FMR20 HART Weight: 4.0 kg (8.82 lb) Material 316L (1.4404) Order number 71452327 Frame, 1 400 mm (55.1 in) 3.2 (0.13) 60 (2.36) ø33.7 (1.3) 4 (0.16) 20 (0.8) 55 (2.17) 109 (4.29) (3.94) 130 (5.12) 150 (5.91) A0037800 ...
Page 53
Micropilot FMR20 HART Accessories Wall bracket for cantilever with pivot 3.2 (0.1) 4 (0.16) ø33.7 (1.3) 6.5 (0.3) 25 (1.0) 88 (3.5) 110 (4.3) 150 (5.9) A0019350 43 Dimensions of the wall bracket. Unit of measurement mm (in) Weight 1.21 kg (2.67 lb)
Micropilot FMR20 HART Accessories 13.1.8 Pivotable mounting bracket The mounting bracket can be ordered together with the device via the product structure "Accessory enclosed". 100 (3.94) 6.8 (0.27) 177 (6.97) 358 (14.1) A0038143 45 Dimensions of pivotable mounting bracket. Unit of measurement mm (in) Material 316L (1.4404)
Accessories Micropilot FMR20 HART 13.1.9 Horizontal mounting bracket The horizontal mounting bracket is used to install the device in confined spaces. The mounting bracket can be ordered together with the device via the product structure "Accessory enclosed". 280 (11) Ø34 (1.34) 9 (0.35)
Micropilot FMR20 HART Accessories 13.1.10 FAU40 alignment unit The alignment unit is used to optimally align the sensor with the bulk solids. 15° 15° (0.39) <360 NPT ¾ (14.2) NPT 1 70 (2.76) 500 (19.7) (0.8) (1.18) 19 (0.75) A0045330 ...
Accessories Micropilot FMR20 HART 13.1.11 Adjustable flange seal The adjustable flange seal is used to align the FMR20 The adjustable flange seal can be ordered together with the device via the product structure "Accessory enclosed". ød øD A0045324 48...
Micropilot FMR20 HART Accessories 13.1.12 RIA15 in the field housing 131 (5.16) 55.5 (2.19) mm (in) A0017722 49 Dimensions of RIA15 in field housing, engineering unit: mm (in) The RIA15 remote indicator can be ordered together with the device. Product structure, feature 620 "Accessories enclosed":...
Page 60
Accessories Micropilot FMR20 HART A0020844 1. Disconnect plug-in terminal block. 2. Insert the terminal block into the slot provided on the HART communication resistor module. 3. Insert the HART communication resistor in the slot in the housing. Endress+Hauser...
• Automatic verification of exclusion criteria • Automatic creation of the order code and its breakdown in PDF or Excel output format • Ability to order directly in the Endress+Hauser Online Shop The Configurator is available on the Endress+Hauser website: www.endress.com...
All the relevant device information, such as the device status, spare parts and device-specific documentation, is available for every device over the entire life cycle. The application already contains the data of your Endress+Hauser device. Endress+Hauser also takes care of maintaining and updating the data records. W@M is available: www.endress.com/lifecyclemanagement...
For dielectric constants (DC values) of many media commonly used in various industries refer to: • the Endress+Hauser DC manual (CP01076F) • the Endress+Hauser "DC Values App" (available for Android and iOS) Operating frequency K-band (~ 26 GHz) Transmission power Mean power density in the direction of the beam •...
Technical data Micropilot FMR20 HART Bluetooth® wireless technology (available as an optional extra) The device has a Bluetooth® wireless technology interface and can be operated and configured via this interface using the SmartBlue app. • The range under reference conditions is 25 m (82 ft) •...
Page 65
Micropilot FMR20 HART Technical data Differing values in near-range applications 30 (1.18) 10 (0.39) 5 (0.2) -5 (-0.2) -10 (-0.39) -30 (-1.18) 0.3 (0.98) 0.5 (1.64) D[m (ft)] A0045305 51 Maximum measured error in near-range applications; values for standard version ∆...
Technical data Micropilot FMR20 HART 14.4 Environment Ambient temperature Measuring device: –40 to +80 °C (–40 to +176 °F) range It may not be possible to use the Bluetooth connection at ambient temperatures > 60 °C (140 °F). Outdoor operation in strong sunlight: •...
Page 67
• Contact Endress+Hauser for lower ε values For dielectric constants (DC values) of many media commonly used in various industries refer to: • the Endress+Hauser DC manual (CP01076F) • the Endress+Hauser "DC Values App" (available for Android and iOS) Endress+Hauser...
Operating menu Micropilot FMR20 HART Operating menu 15.1 Overview of the operating menu (SmartBlue) Navigation Operating menu Main menu ‣ Setup → 76 ‣ Basic setup Device tag Distance unit Empty calibration Full calibration Distance Level Signal quality ‣...
Page 69
Micropilot FMR20 HART Operating menu First Echo sensitivity Output mode Blocking distance Level correction Evaluation distance Linearization type Level linearized ‣ Safety settings → 84 Delay time echo lost → 84 Diagnostics echo lost → 84 ‣...
Page 70
Operating menu Micropilot FMR20 HART Device reset → 88 Free field special → 89 ‣ → 90 Communication ‣ HART configuration HART short tag HART address No. of preambles ‣ HART info Device type Device revision Device ID...
Page 71
Micropilot FMR20 HART Operating menu Relative echo amplitude (TV) Temperature (QV) ‣ Bluetooth configuration → 93 Bluetooth mode → 93 ‣ Diagnostics → 94 ‣ Diagnostics → 94 Actual diagnostics → 94 Previous diagnostics → 94 Delete previous diagnostic →...
Operating menu Micropilot FMR20 HART 15.2 Overview of operating menu (FieldCare / DeviceCare) Navigation Operating menu Main menu ‣ Setup → 76 → 76 Device tag Distance unit → 76 Empty calibration → 76 Full calibration →...
Page 73
Micropilot FMR20 HART Operating menu Level linearized → 83 ‣ → 84 Safety settings Delay time echo lost → 84 Diagnostics echo lost → 84 ‣ Current output → 85 Output current → 85 Damping output →...
Page 75
Micropilot FMR20 HART Operating menu Serial number → 97 → 97 ENP version ‣ Simulation → 98 Simulation → 98 Value current output 1 → 98 Process variable value → 98 Endress+Hauser...
Operating menu Micropilot FMR20 HART 15.3 "Setup" menu • : Indicates navigation to the parameter via operating tools • : Indicates parameters that can be locked via the access code. Navigation Setup Device tag Navigation Setup → Device tag...
Micropilot FMR20 HART Operating menu User entry 0.0 to 20 m Factory setting Depends on the antenna version Distance Navigation Setup → Distance Description Shows the distance D that is currently measured from the reference point (lower edge of flange / last thread of sensor) to the level.
Page 78
Operating menu Micropilot FMR20 HART User interface • Strong • Medium • Weak • No signal Confirm distance Navigation Setup → Confirm distance Description Does the measured distance match the real distance? Select one of the options: - Manual map To be selected if the range of mapping is to be defined manually in the ' M apping end point' parameter.
Page 79
Micropilot FMR20 HART Operating menu User interface 0 to 100 m Endress+Hauser...
Operator to the Maintenance mode. The device remains in the Operator mode if an incorrect access code is entered. If you lose the access code, please contact your Endress+Hauser sales center. User entry...
Page 81
Micropilot FMR20 HART Operating menu Changing velocity Navigation Setup → Advanced setup → Changing vel. Description Selection of the expected draining or filling speed of the measured level. Selection • Slow <10 cm (0,4 in)/min • Standard <1 m (40 in)/min •...
Page 82
Operating menu Micropilot FMR20 HART Blocking distance Navigation Setup → Advanced setup → Blocking dist. Description Specify blocking distance (BD). No signals are evaluated within the blocking distance. Therefore, BD can be used to suppress interference signals in the vicinity of the antenna.
Micropilot FMR20 HART Operating menu Linearization type Navigation Setup → Advanced setup → Lineariz. type Description Linearization types Meaning of the options: • None: The level is output in the level unit without being converted (linearized) beforehand. • Table: The relationship between the measured level L and the output value (volume/flow/ weight) is defined by a linearization table.
Operating menu Micropilot FMR20 HART "Safety settings" submenu Navigation Setup → Advanced setup → Safety sett. Delay time echo lost Navigation Setup → Advanced setup → Safety sett. → Delay echo lost Description Define the delay time in the case of an echo loss.
Micropilot FMR20 HART Operating menu "Current output" submenu Navigation Setup → Advanced setup → Curr.output Output current Navigation Setup → Advanced setup → Curr.output → Output curr. Description Shows the actual calculated value of the output current. User interface 3.59 to 22.5 mA...
Operating menu Micropilot FMR20 HART 4 mA value Navigation Setup → Advanced setup → Curr.output → 4 mA value Description Value for 4-mA at ' T urn down parameter' = On Using the turn down functionality it is possible to map a section of the measuring range to the total range of the output current (4-20mA).
Micropilot FMR20 HART Operating menu Trim Navigation Setup → Advanced setup → Curr.output → Trim Description Select action for the recalibration of the current output. The trim can be used to compensate a drift of the current output (which might be caused by very long cables or by a connected Ex barrier, for example).
' E nter access code' parameter. The new access code is only valid after it has been confirmed in the ' C onfirm access code' parameter. Please contact your Endress+Hauser Sales Center if you lose your access code. User entry 0 to 9 999 Confirm access code ...
Page 89
Micropilot FMR20 HART Operating menu Free field special Navigation Setup → Advanced setup → Administration → Free field spec. Description Switch the free field option on or off. This parameter can be switched on for free field applications (e.g. below bridges).
Operating menu Micropilot FMR20 HART 15.3.2 "Communication" submenu Navigation Setup → Communication HART short tag Navigation Setup → Communication → HART short tag Description Short description of the measuring point User entry Max. 8 characters: A ... Z, 0 ... 9 and some special characters (for example, punctuation...
Page 91
Micropilot FMR20 HART Operating menu Device revision Navigation Setup → Communication → Device revision Description Shows the device revision with which the device is registered with the HART Communication Foundation. Device ID Navigation Setup → Communication → Device ID Description Shows the device ID for identifying the device in a HART network.
Page 92
Operating menu Micropilot FMR20 HART Hardware revision Navigation Setup → Communication → Hardware rev. Description Indicates hardware revision of the device Software revision Navigation Setup → Communication → Software rev. Description Indicates software revision of the device HART date code ...
Micropilot FMR20 HART Operating menu Relative echo amplitude (TV) Navigation Setup → Communication → Rel.echoampl(TV) User interface Signed floating-point number Temperature (QV) Navigation Setup → Communication → Temperature (QV) User interface Signed floating-point number "Bluetooth configuration" submenu Navigation ...
Operating menu Micropilot FMR20 HART 15.4 "Diagnostics" submenu Navigation Diagnostics Actual diagnostics Navigation Diagnostics → Actual diagnos. Description Displays current diagnostic message. If several messages are active at the same time, the messages with the highest priority is displayed.
Page 95
Micropilot FMR20 HART Operating menu Signal quality Navigation Diagnostics → Signal quality Description Displays the signal quality of the level echo. Meaning of the display options - Strong: The evaluated echo exceeds the threshold by at least 10 dB.
Operating menu Micropilot FMR20 HART 15.4.1 "Device information" submenu Navigation Diagnostics → Device info Device name Navigation Diagnostics → Device info → Device name Description Shows the name of the transmitter. User interface Character string comprising numbers, letters and special characters (#16)
Micropilot FMR20 HART Operating menu Extended order code 3 Navigation Diagnostics → Device info → Ext. order cd. 3 Description Shows the 3rd part of the extended order code. User interface Character string comprising numbers, letters and special characters (#20)
Operating menu Micropilot FMR20 HART 15.4.2 "Simulation" submenu Navigation Diagnostics → Simulation Simulation Navigation Diagnostics → Simulation → Simulation Description Select process variable to be simulated. The Simulation is used to simulate specific measuring values or other conditions. This helps to check the correct configuration of the device and connected control units.