Group 3: Output Function Parameters
03 - 00
Multi-function Output terminal 1 (Relay)
Settings
Setting
Functions
00
Disabled
01
Indication during
operation
02
Master frequency
attained
03
Zero Speed (including
shutdown)
04
Over-torque
05
External Fault
06
Low voltage detection
07
Operation Mode
indication
08
Fault Indication
09
Master Frequency
Attained 1
10
Master Frequency
Attained 2
11
Over Temperature
indication
12
Drive Ready
13
External Emergency Stop
(EF1)
14
Software braking output
15
OL or OL1 overload
warning
16
Low current indication
Revision July 2008, EG03, SW V1.06
00-21
The corresponding output will be closed during operation
(including DC braking time).
The corresponding output will be closed when output
frequency reaches master frequency command.
The corresponding output will be closed when the AC drive
has no output voltage signal.
The corresponding output relay will be closed when the AC
drives output current exceeds the over-torque detection
level 06-04.
The corresponding output will be closed when the EF is
enabled. (Pr. 04-00 to 04-03)
The corresponding output will be closed when the DC Bus
voltage drops below our threshold. The keypad will display
"Lu".
The corresponding output will be closed when the AC
drives "Operation Command" is controlled by the external
terminals.
The corresponding output will be closed when AC drive
has experienced a fault.
The corresponding output will be closed when the AC
drives output frequency exceeds (Pr.03-08) Master
Frequency Attained 1.
The corresponding output will be closed when the AC
drives output frequency exceeds (Pr.03-09) Master
Frequency Attained 2.
The corresponding output will be closed when the AC drive
temperature exceeds its rating.
The corresponding output will be closed the when the AC
drive is ready and has no faults.
The corresponding output will be closed when multi-
function input terminals (Pr.04-00 to 04-03) are set to
emergency stop and then activated.
The corresponding output will be closed when the AC
drives DC bus voltage exceeds (Pr.08-19) the braking
level.
The corresponding output will be closed upon an overload
(OL or OL1) fault.
The corresponding output will be closed when the AC
drives output current is lower than the Low Current setting
(Pr.06-08).
Chapter 4 Parameters|
Factory Setting: 01
Descriptions
4-37