Rtu-Mp/Indoor Co2 Sensor (33Zcsenco2) Connections; Rtu-Mp/Outdoor Co2 Sensor (33Zcsenco2) Connections; Connecting Discrete Inputs; Filter Status - Carrier 50TC Installation Instructions Manual

Single package rooftop, 50hz cooling only sizes 07, 08, 09, and 12 with puronr (r-410a) refrigerant
Hide thumbs Also See for 50TC:
Table of Contents

Advertisement

To wire the return air enthalpy sensor, perform the
following:
1. Use a 2- - conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
2. At the enthalpy control remove the factory- - installed
resistor from the (SR) and (+) terminals.
3. Connect the field- - supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air
enthalpy sensor and the (SR) terminal on the enthalpy
controller.
NOTE: The enthalpy control must be set to the "D"
setting for differential enthalpy control to work properly.
Indoor Air Quality (CO
sensor) — The indoor air quality
2
sensor accessory monitors space carbon dioxide (CO
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO
present in the space air.
2
The CO
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
requirements and terminal locations. See Fig. 37 for
typical CO
sensor wiring schematic.
2
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return- - air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2- - conductor 18 AWG (American
Wire Gage) twisted- - pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the RTU- - MP control board
terminals.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 36. Connect the 4- - 20 mA terminal to
RTU- - MP J4- - 2 and connect the SIG COM terminal to
RTU- - MP J4- - 3. See Fig. 51.
)
2
sensor for electrical
2
2
IAQ Sensor
SEN
COM
24 VAC
Fig. 51 - - RTU- - MP / Indoor CO
(33ZCSENCO2) Connections
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO
designed to monitor carbon dioxide (CO
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
with an outdoor cover. See Fig. 39. The outdoor air CO
sensor must be located in the economizer outside air hood.
Wiring the Outdoor Air CO
supply is required for this sensor. A two- - wire cable is
required to wire the dedicated power supply for the sensor.
The two wires should be connected to the power supply
and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 37. Connect the 4 to 20 mA
terminal to RTU- - MP J4- - 5. Connect the SIG COM
terminal to RTU- - MP J4- - 6.
OAQ Sensor/RH Sensor
SEN
COM
24 VAC
Fig. 52 - - RTU- - MP / Outdoor CO
(33ZCSENCO2) Connections

Connecting Discrete Inputs

Filter Status

The filter status accessory is a field- - installed accessory.
This accessory detects plugged filters. When installing
this accessory, the unit must be configured for filter status
by setting MENU
Config
to Filter Status and normally open (N/O) or normally
closed (N/C). Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 45 and Fig. 47 for wire
terminations at J5.
31
J4-2
J4-3
C08462
Sensor
2
sensor is
2
) levels in the
2
Sensor — A dedicated power
2
J4-5
J4-6
C08463
Sensor
2
Inputs
input 3, 5, 8, or 9
2