Premierlink Controller; Typical Mounting Location For Supply Air Temperature (Sat) Sensor On Small Rooftop Units - Carrier 50TC Installation Instructions Manual

Single package rooftop, 50hz cooling only sizes 07, 08, 09, and 12 with puronr (r-410a) refrigerant
Hide thumbs Also See for 50TC:
Table of Contents

Advertisement

PremierLinkt (Factory- -Option) —
The PremierLink controller (see Fig. 27) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory- - defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display tools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory- - mounted in the 50TC
unit's main control box to the left of the Central Terminal
Board (CTB). Factory wiring is completed through
harnesses connected to the CTB pin connectors. Field
connections are made at a 16- - pole terminal block (TB1)
located on the bottom shelf of the unit control box in front
of the PremierLink controller. The factory- - installed
PremierLink control includes the supply- - air temperature
(SAT) sensor. The outdoor air temperature (OAT) sensor is
included in the FIOP/accessory EconoMi$ert2 package.
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE:
PremierLink controller is shipped in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
Supply
Air
Temperature
FIOP- - equipped 50TC unit, the unit is supplied with a
supply- - air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 152 mm
(6- - inches) in length. It is a nominal 10- - k ohm thermistor.
Fig. 27 - - PremierLink Controller
(SAT)
Sensor
On
The SAT is factory- - wired. The SAT probe is wire- - tied to
the supply- - air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re- - position the sensor in the flange of the supply- - air
opening or in the supply air duct (as required by local
codes). Drill or punch a 12.7 mm (
flange or duct. Use two field- - supplied, self- - drilling
screws to secure the sensor probe in a horizontal
orientation. See Fig. 28.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
Fig. 28 - - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
NOTE:
Refer to Form 33CS- - 58SI for complete
PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start- - up.
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit's heater surfaces.
18