Economizer Controls

Indoor Air Quality (CO
) Sensor —
2
The indoor air quality sensor accessory monitors space
carbon dioxide (CO
) levels. This information is used to
2
monitor IAQ levels. Several types of sensors are available,
for wall mounting in the space or in return duct, with and
without LCD display, and in combination with space
temperature sensors. Sensors use infrared technology to
measure the levels of CO
present in the space air.
2
The CO
sensors are all factory set for a range of 0 to
2
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO
requirements and terminal locations. See Fig. 47 for
typical CO
sensor wiring schematic.
2
H G 24 VAC
OR
+ -
24 VDC
2 1
8 7 6 5 4 3 2 1
J3
J4
Fig. 47 - - Indoor/Outdoor Air Quality (CO
(33ZCSENCO2) - - Typical Wiring Diagram
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return- - air
grille (if present) so it senses the concentration of CO
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
Wiring the Indoor Air Quality Sensor: For each sensor,
use two 2- - conductor 18 AWG (American Wire Gage)
twisted- - pair cables (unshielded) to connect the separate
isolated 24 vac power source to the sensor and to connect
the sensor to the control board terminals.
sensor for electrical
2
+
0-10VDC
-
SIG COM
+
4-20mA
NC
}
ALARM
COM
RELAY
NO
CONTACTS
C08635
) Sensor
2
2
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 47. Connect the 4- - 20 mA terminal to
terminal TB1- - 9 and connect the SIG COM terminal to
terminal TB1- - 11. See Fig. 48.
IAQ Sensor
SEN
COM
24 VAC
Fig. 48 - - Indoor CO
Connections
Refer to the PremierLinkt Installation, Start- - up, and
Configuration Instructions, for detailed configuration
information.

Outdoor Air Quality Sensor

(PNO 33ZCSENCO2 plus weatherproof enclosure) —
The outdoor air CO
sensor is designed to monitor carbon
2
dioxide (CO
) levels in the outside ventilation air and
2
interface with the ventilation damper in an HVAC system.
The OAQ sensor is packaged with an outdoor cover. See
Fig. 49. The outdoor air CO
economizer outside air hood.
COVER REMOVED
Fig. 49 - - Outdoor Air Quality Sensor Cover
Wiring the Outdoor Air CO
power supply is required for this sensor. A two- - wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 47. Connect the 4 to 20 mA
terminal to the TB1- - 13 terminal of the 50TC. Connect the
SIG COM terminal to the TB1- - 11 terminal of the 50TC.
See Fig. 50.
29
TB1
9
J5-5
TB1
7
J5-6
C08636
Sensor (33ZCSENCO2)
2
sensor must be located in the
2
SIDE VIEW
C07135
Sensor: A dedicated
2
PL